Search results

  1. K

    Master Switch MEP 803a replacement compatibility?

    The switch in the first post will NOT replace your S1 Master Start switch. I assume your S1 switch is a blue plastic one. Failure prone for sure. Ideally, you'd want to replace it with an Electro Switch 75902LV. They will last a lifetime, but are pricey. You could replace it with a 88-21160...
  2. K

    Undervoltage light on MEP-804A

    Got it, Thx!
  3. K

    Undervoltage light on MEP-804A

    No need to check T1 if using my VR. My VR doesn't use T1. :)
  4. K

    Undervoltage light on MEP-804A

    You'll want to test the T1 transformer to be sure it's working. They fail with some frequency.
  5. K

    Undervoltage light on MEP-804A

    Looks like someone put a LIBBY AC Voltage Regulator in by mistake! The Transformer T1 in your picture is a TRC Transformer for a TRC AC Voltage Regulator setup. The front panel potentiometer R1 is a 20K ohm one which is for a TRC AC Voltage Regulator setup. You don't have a picture of R16. R16...
  6. K

    Undervoltage light on MEP-804A

    That's NOT the test procedure for the LIBBY AC Voltage Regulator. That's one is for the TRC AC Voltage Regulator. The one for the LIBBY is -24 TM dated 1 May 2008 paragraph 4-1.1 4-1.1 Testing (AC Voltage Regulator, P/N 01-21501-1, for MEP-804A/MEP-804B). a. Shut down generator set. b...
  7. K

    Undervoltage light on MEP-804A

    That would be the LIBBY AC Voltage Regulator
  8. K

    Undervoltage light on MEP-804A

    I'd suggest performing the AC Voltage Regulator Test per the -24 TM. Be sure to use the correct test procedure. The 804's were built with two different AC Voltage Regulator systems. Libby & TRC. Different test procedures depending on which VR is in the set. You'll also want to verify someone...
  9. K

    Mep831a Yanmar engine repurpose

    Yes, I'm still making them. Per forum rules one can only have a few listings in the Classifieds section.
  10. K

    MEP802 Short

    If no mouse issues or chaffed wires then I'd highly suspect one or more of the contacts in the Phase/Voltage switch are welded closed. Each switch contact relies on a tiny spring to open the contacts.
  11. K

    mep-831a how to backfeed to OFF GRID electric panel to charge solar bank or run house

    I sent you a PM here on S.S. regarding your eBay question. Kurt
  12. K

    mep804B field winding diagram

    I assume you mean the stator windings and not the field winding. There is just 1 field winding.
  13. K

    mep-831a how to backfeed to OFF GRID electric panel to charge solar bank or run house

    You need to close the circuit interruptor using the toggle switch on the front panel to get power to the lugs. Wait 5 seconds after starting the 831 before lifting and releasing the switch.
  14. K

    MEP-831A no output at outside 240 terminals?Have 120v at the plug though

    There are three relays behind the drop down meter panel. They all have a tiny LED in them. After your start the 831 which relay(s) have their LEDs illuminated? Also, after you start it are there any fault lamps illuminated on the Fault Monitor?
  15. K

    Mep 831a

    TM indicates: Four-gallon fuel tank (allowing 8 hours of continuous operation at full load) You'll want to mouse proof it to keep those Bastids out. Running for days on end will require an auxiliary fuel tank for it to draw diesel from. Oil is supposed to be changed every 100 hours of...
  16. K

    MEP-831A no output at outside 240 terminals?Have 120v at the plug though

    The circuit interrupter switch is pretty reliable. The outlet is hardwired so it only has 120 volts on it all the time. The little red switch only changes the power at the lugs. You'll need to connect L0 to you electrical systems neutral. If you don't the two 120 volt branches voltages will...
  17. K

    MEP-831A no output at outside 240 terminals?Have 120v at the plug though

    Did you lift and then release the Contactor toggle switch to close the contactor after it's started and running for 10 seconds? Opening the door to access the lugs does not cut power to them.
  18. K

    MEP-803A wiring, internal and external

    The set is only spec'd to go up to 220 in 3 phase.
  19. K

    MEP-531a LOP cable

    That info would be in the Technical Manual for the set. TM 9-6115-673-13&P Available here -----> MEP-531A TM