  1. K

    MEP-803A won’t start and making a terrible noise.

    In the video it appears that the set is just being started and the bad noise comes and goes for a few seconds and then stops. My guess is that the "crank disconnect" circuit in the set is failing causing the starter to grind during the start cycle. The crank disconnect circuit is there to...
  2. K

    Picked up 804a and 802a today and looking for advise.

    Wow, what a difference!
  3. K

    MEP-806A Transformer Replacement Part

    Yes, you have it exactly correct. You may not be able to PM me yet but my email address is in the listing.
  4. K

    802 relay assist

    PM me if you need any. I have 6 or so new ones available. Kurt
  5. K

    MEP-806A Transformer Replacement Part

    Shook up:) Click on my signature below to get to my listings in the forum classifieds. Or click this -> Listings
  6. K

    MEP-804A Under Voltage Fault

    CR2 is not the static exciter coil. CR2 is just a diode in the circuit that provides the flashing voltage to the static exciter. F- and F+ shown above go to the VR terminals 1 & 3 and then on to the static exciter via P5 pins 28 & 29
  7. K

    MEP-804A Under Voltage Fault

    24 is way to high. Disconnect the wires from VR terminals 1 and 3. Measure the resistance between those two wires. It should be 28 to 38 ohms. This is checking continuity to and the resistance of the static Exciter coil.
  8. K

    MEP-804A Under Voltage Fault

    Need to measure DC voltage there, not AC. Should be about 10 volts DC with S1 in Start.
  9. K

    MEP-804A Under Voltage Fault

    Terminal 2 on the factory VR and my VR do not get any wires connected to them. The wires that were on the factory VR get hooked to the same terminal numbers on my VR.
  10. K

    MEP-804A Under Voltage Fault

    Double checking.. The generator was putting out correct voltage just before T1 smoked? Now with T1 yanked no AC voltage even with S1 in Start? If so circle back and check the DC voltage across VR terminals 1 & 3 with S1 in Start
  11. K

    MEP-804A Under Voltage Fault

    Yup
  12. K

    MEP-804A Under Voltage Fault

    Ditto. Ignore the other TRC stuff. Not involved with AC voltage regulation. Just disconnect T1 completely. Isolate each of the leads. T1 is not needed or used with my VR. Per our conversation the other day T1 seemed to have a problem since it was dragging the 208 input down.
  13. K

    MEP-804A Under Voltage Fault

    I tested R4 & R5 in two Libby VR's I have here. In one VR R4 & R5 both measured 2.405 K Ohms each when measured in circuit. Polarity didn't make any difference. In the other VR R4 & R5 both measured 2.415 K Ohms each when measured in circuit. Polarity didn't make any difference.
  14. K

    Picked up 804a and 802a today and looking for advise.

    Removing the fuse or the wire from VR terminal 8 will kill power TO the VR. However doing that does not stop the flashing function and the gen head will still generate power when S1 is in START. A better way is to disconnect the P5 plug. This will disconnect power to the VR and prevent the...
  15. K

    MEP802A Rollin Coal - Needs Stator

    Having wires 6 and 9 reversed would cause the windings in the stator to be incorrectly configured. All that current would have passed thru the contacts of S8 the phase voltage switch possibly welding some of its contacts together. It's tedious but you'll want to test S8 to verify all contacts...
  16. K

    MEP-804A Under Voltage Fault

    An Over Voltage Fault would be the AC output. That R5 looks crispy. Will take a close look at a couple of factory VRs I have laying around.
  17. K

    MEP 802A M8 Percent Load Gauge Issue

    Actually they are not potted on the inside. Someone posted a pic a few years ago of a CT opened up. Just 3 separate coils suspended by the plastic housing. ** Warning If the output of a CT doesn't have a load on it, it can generate extremely high, lethal voltage
  18. K

    MEP-802A Starter problem?

    From the -24 TM
  19. K

    MEP-804A No AC power when start switch is released.

    When shuts down are any of the Fault lamps illuminated?
  20. K

    24 Volt battery maintainer?

    You can leave the batteries hooked up in series when using two 12v chargers. Yes hook each charger to each battery. The only time you can't do this is with chargers with a 3 pin ac plug and battery charger negative is connect to the ac plug ground pin. Ask me how I know :LOL: