  1. K

    Thoughts on 12v conversion on MEP-831A and MEP-803A possible or not?

    If you need the glow plugs for cold starting you'd need to modify their wiring to get 12v to each heater element.
  2. K

    Thoughts on 12v conversion on MEP-831A and MEP-803A possible or not?

    Another gotcha on the 803. You'll need 24 volts for the fuel solenoid to retract to allow the engine to start.
  3. K

    Thoughts on 12v conversion on MEP-831A and MEP-803A possible or not?

    Like the 831 the 802 can generate it's own 24 volts with the alternator. An 802 will run without batteries. They are only needed to start it or 24 volts in thru the slave port to get it started. The minor hitch is the alternators exciter will need 24 volts momentarily to get it generating 24...
  4. K

    MEP-831A will not start air compressor

    You are correct, there is no typical circuit breaker on the 831 for the power to the lugs. The inverter monitors the current load on L1 & L2 coming out of the inverter. If the current monitor detects current in excess of the rated current it causes the contactor to open. There isn't any way to...
  5. K

    Mep-1050 control box

    Yes
  6. K

    Mep-1050 control box

    Relay Panel Circuit Breaker locations inside it
  7. K

    Mep-1050 control box

    That's the main circuit breaker, CB 201, by the batteries and starting solenoid. What about CB 7 in the Relay Panel RP201? Reset? Missing?
  8. K

    Mep-1050 control box

    Did it work previously for you? Are the batteries charged? Is the main circuit breaker ON by the batteries? Circuit Breaker #7 in the Relay Panel RP201 powers the "control box" DCS". Is it tripped or missing?
  9. K

    MEP-831A will not start air compressor

    In general motor driven items draw about 4X the nameplate current at startup until they get up to speed. That high startup current is what's tripping the 831.
  10. K

    MEP-804A Smoke, what is the cause?

    Injection Pump
  11. K

    24 Volt Control Voltage. I have it here but not over there!

    MajorGasAttak - For starters, what model of generator are you working on? Do you have a copy of the relevant TM with the schematics in it?
  12. K

    MEP-804A Coolant Temperature Sender Part Number

    You can use Parttarget.com to get all the PNs for or a given NSN or PN. Put in 5905-01-392-8825 and you'll be get: 126864 06555 Beede Electrical Instrument Co. Inc. A A 88-22322 30554 Department of Defense Project A A 02094-00 1NBV2 Maxima Technologies A F 02094-00 16476 Maxima...
  13. K

    MEP-805A T1 Issue

    He's all set.
  14. K

    MEP-831a Inverter Overhaul

    I tested the diodes on both of my diode boards with my Fluke. *All diodes measured about .45V and infinity (after the caps charged from my meter) * Actually I found one of my diodes shorted.
  15. K

    MEP-831a Inverter Overhaul

    Not fixing it. It's one of several dead inverters I have laying around here. I use it for pictures only. The charring is from a trace that vaporized. It was the Load signal from the inverter going to the Governor Controller module. IC's are ON Semiconductor.
  16. K

    MEP-831a Inverter Overhaul

    Could be why so many of the inverters fail.
  17. K

    MEP-831a Inverter Overhaul

    Peter, Here are front and back pics of the same part on the top board. Ref Des on the PCB for it is C19 No marking on the back
  18. K

    MEP-831a Inverter Overhaul

    Peter, No inrush limiter. DC goes from diode bridge directly to the electrolytics. Only other parts on the assembly besides the two disc caps are a couple of caps between the power transistors and two bleeder resisters. I suspect it doesn't need a limiter since the PMA voltage rises as the...
  19. K

    MEP-831a Inverter Overhaul

    I'll tear my inverter down more and see if there is an inrush limiter.
  20. K

    MEP-831a Inverter Overhaul

    Here's a picture of one.