  1. Light in the Dark

    MEP-803a overload circuit

    Stuff is magic. I have a 10k here that was going into overload at under 8KW (while simultaneously showing only 20% on the load gauge) just a couple of days ago. Being so cold I sprayed and exercised and came back the next day and just like it left the factory.
  2. Light in the Dark

    MEP-803a overload circuit

    Did you take any time cleaning the terminal boards in this same area, and retightening all screws there too?
  3. Light in the Dark

    MEP-803a overload circuit

    Hello. Yeah the S8 cleaned up just fine, and got full functionality back (with no overload condition up to 13.5kw). Forgot to circle back on this. Thanks for the reminder.
  4. Light in the Dark

    MEP-803a overload circuit

    Well this machine is an 04, reset in 08 or 10.
  5. Light in the Dark

    MEP-803a overload circuit

    I don't know when they made the vendor change, but like you have said a few times, thats an irrelevant figure. This one was dusty in the rear of the control box, so certainly with the liberal washing it got... I hope the next owner will be problem free. She tested fine.
  6. Light in the Dark

    MEP-803a overload circuit

    I am not sure if its new or old... blue plastic body with Kraus & Naimer info. The machine has been closed back up and moved out of the garage.
  7. Light in the Dark

    MEP-803a overload circuit

    That's awesome Guy, the forum thanks you. I took the operator cover off this morning, and set to checking all TBs, all connections, and to bathe the S8 in deoxit, like it was visiting a Turkish spa. I found two wires on a TB that were not loose, but could take an additional 1/16th of a turn. I...
  8. Light in the Dark

    MEP-803a overload circuit

    It was also doing this when testing 5.4 + 2.7kw. Does anyone have a simple wire schematic for the S8 that is cleaned up? What seems more likely here... something is miswired on the S8, or that the S8 might be faulty?
  9. Light in the Dark

    MEP-803a overload circuit

    Ok so riddle me this, Batman... So I have a little bit of time to play with this today. Just hooked up the bank, and got it to temp and flipped it on. So I am getting about 8 minutes of run under load (about 75% on the gauge, about 10.8kw of dryer element). So the generator is still...
  10. Light in the Dark

    MEP-803a overload circuit

    Ok, so I misspoke (or was not clear). So the overload light was still coming on. I did not take the additional step of running with the battle short on (I really shouldnt have been out there messing with the set to begin with, so I wasn't going to push my luck). I will though, and will check the...
  11. Light in the Dark

    MEP-803a overload circuit

    Oh yeah, great combo. By the time I came back from the doctors office around noon, my wife had prepared a bone broth for me. She's a keeper. My next guess as to what the problem might be here, are the burden resistors. Thoughts?
  12. Light in the Dark

    MEP-803a overload circuit

    So, the new K8 did not fix the problem. It is still going into overload condition. AND.. I have pneumonia. Fun all around. Getting 12-18" of snow tonight, so I have it out back, knowing it will run our place just fine until I can get back to it (we have very little draw requirement).
  13. Light in the Dark

    MEP-803a overload circuit

    20c sounds like a wonderful temp for a ride! I used to head west every winter for a round of trade shows, in the process, trading New England February for mid 60s Southern California. The locals would be scurrying around in coats... I'm just looking for a nice outdoor cafe to grab a bite at to...
  14. Light in the Dark

    MEP-803a overload circuit

    I believe that would be "Open -10 manual" ;). I just dropped the project and came in for lunch and to post the question, experiencing ultimate frustration. You finally shake your sickness?
  15. Light in the Dark

    MEP-803a overload circuit

    I must have hit the emergency stop when reassembling the control box hinge... **** do I feel dumb. I owe kloppk a six pack, I think. I was so frustrated (I've had this laryngitis for like 3 weeks now) that it had taken that long to do the swap over (though I was very certain to make sure to...
  16. Light in the Dark

    MEP-803a overload circuit

    Ok, so before I go burn my garage down with everything in it.... So I swapped the K8. All of the wires appeared to be put in place correctly (and I believe I did my due diligence in putting them all back in position)... So now I have NO power at the set at all. The dead crank works... but when...
  17. Light in the Dark

    MEP-803a overload circuit

    I will check the wires when I have the new part in my hand, during reinstall. Will circle back on this. Thanks for everyone's help.
  18. Light in the Dark

    MEP-803a overload circuit

    Just grabbed one off that auction place. I hope to swap it out this week, and have it readily fix the problem. Been innundated with calls for gensets in the last 48 hours. Happens after every major storm.
  19. Light in the Dark

    MEP-803a overload circuit

    So this set has about 1400 hours since Tier Reset... so I guess its possible its had a wiring fault this whole time, but I would think that maybe thats not as likely? It does seem perplexing that its still dumping the load with the battle short on, which is why I post here. I will look at the...
  20. Light in the Dark

    MEP-803a overload circuit

    No, the short circuit light did not come on.