I have had this generator for 2 years now. It’s a known runner, that I’ve run for hours at a time without issue. Unit has ~120 hours per the meter and has not been reset.
I started it up today and closed the S5 and the light didn’t illuminate. Turned my load on to find out that I didn’t have my power. I pulled out the multi meter to find that I do have 120v at the convenience outlets. M2 frequency meter registers 60hz and M1 voltage gauge registers 240v. Unit is set up for 120/240 single phase. S6&S8 are in the correct positions.
What’s random is after a few startup/shutdowns while trouble shooting, the unit produced power twice for ~8-10 minutes each pulling an~45amps @ 240v resistive load. Each time the output terminals lost power the convenience outlets, M1 & M2 all continued to register as normal.
Steps I’ve taken:
**I exercised the S6 and S8 thinking that maybe corrosion was causing the issue, no change.
**used TM 9-6115-642-24 to try and test the S5 per 2-51.1 and 2-51.2.
I have not tested the K1 as I’d like to exhaust all options before removing the top cover.
Questions:
(1) What pins on the S5 should actually have continuity while the unit is off and battery disconnected?
(2) What pins on the S5 should have continuity while holding the S5 in the closed position Withrow the unit off and battery disconnected.
(3) What pins on the S5 should have continuity while holding the S5 in the open position Withrow the unit off and battery disconnected.
Also, what is the likelihood that either my S5 or K1 randomly failed?
Sent from my iPhone using Tapatalk
I started it up today and closed the S5 and the light didn’t illuminate. Turned my load on to find out that I didn’t have my power. I pulled out the multi meter to find that I do have 120v at the convenience outlets. M2 frequency meter registers 60hz and M1 voltage gauge registers 240v. Unit is set up for 120/240 single phase. S6&S8 are in the correct positions.
What’s random is after a few startup/shutdowns while trouble shooting, the unit produced power twice for ~8-10 minutes each pulling an~45amps @ 240v resistive load. Each time the output terminals lost power the convenience outlets, M1 & M2 all continued to register as normal.
Steps I’ve taken:
**I exercised the S6 and S8 thinking that maybe corrosion was causing the issue, no change.
**used TM 9-6115-642-24 to try and test the S5 per 2-51.1 and 2-51.2.
I have not tested the K1 as I’d like to exhaust all options before removing the top cover.
Questions:
(1) What pins on the S5 should actually have continuity while the unit is off and battery disconnected?
(2) What pins on the S5 should have continuity while holding the S5 in the closed position Withrow the unit off and battery disconnected.
(3) What pins on the S5 should have continuity while holding the S5 in the open position Withrow the unit off and battery disconnected.
Also, what is the likelihood that either my S5 or K1 randomly failed?