• Steel Soldiers now has a few new forums, read more about it at: New Munitions Forums!

  • Microsoft MSN, Live, Hotmail, Outlook email users may not be receiving emails. We are working to resolve this issue. Please add support@steelsoldiers.com to your trusted contacts.

Search results

  1. Denvercaitland

    Mep803a final hookup and first load test.

    . Short video when first applied 52A. Smoking a bit, but seemed to have cleared up. Will double check during daylight this weekend.
  2. Denvercaitland

    Mep803a final hookup and first load test.

    Using my 2 radiant heater, the f18h heater, and a 4800w shop heater brings me to 52 A at 240v . With added bonus that the load bank is heating the shop ;)., I added the shelter before the storm this AM and noise level is reasonable at approx 15 feet
  3. Denvercaitland

    Mep803a final hookup and first load test.

    Ran the set for 3 hours tonight split between 60% ,80% and 100% load. First time running for any length but If anything it run smoother now that it worked for an hour at 100%. . All the numbers look good at 52A.. found an old post from guyfang suggesting to close K1 before applying...
  4. Denvercaitland

    Mep803a final hookup and first load test.

    Will do. Thanks
  5. Denvercaitland

    Mep803a final hookup and first load test.

    Found the exact terminal on S8 for amp meter. Will have a closer look after work
  6. Denvercaitland

    Mep803a final hookup and first load test.

    I read about contact cleaners on the forum. And have a can of deoxit on order should be here by the weekend. Outside Temp hovering in the -5° to - 10 °F with major snowstorm coming, should have waited a few more days before moving the 803 outside :). Had to do major surgery to the bodywork...
  7. Denvercaitland

    Mep803a final hookup and first load test.

    Moved the 803 to its permanent location , and did initial load test. The double throw switch and sub panel in the shop worked as planned. Loaded at 20.6A -46.12A - 54.37A. Water temp constant at 190°, oil pressure 40psi ,Hz from 60.5 at no load to 59.5 at 54.37 I reviewed a post from KennyO...