    Mep-002a gets 240 at the lugs, but control box gauge says 120.

    Well, If I was to just say, hmm.... I sure thought I had that switch set to 1 L3-L1 L3. But no, I had it set to 5:00 position, 1 L3-L0 L3. Could have sworn I had that put right. Well, it all works now, thanks to yall. Bone head move on my part, thanks again guys.
  2. C

    Mep-002a gets 240 at the lugs, but control box gauge says 120.

    I Have had it for about 12 years, it was working fine, then about 4 years ago it started overvolting, 300-316 at the lugs 160-170 at the outlet, I bought a new voltage regulator off of here (Mr Jim I think? it has been a few years) and that did not fix it, I replaced the T1 and T2 transformers...
  3. C

    Mep-002a gets 240 at the lugs, but control box gauge says 120.

    I read the L1 and L3 and get 240, I read l1 and L0 get 120, and L3 and L0 and get 120, that is all working correctly, there is only 2 terminals on the back of the voltage meter in the control cabinet, and when measured on them, it only gets 120, which is what the gauge reads. What makes the...
  4. C

    Mep-002a gets 240 at the lugs, but control box gauge says 120.

    it gets 240 at the lugs, but control box gauge says 120. I have put a Fluke on the back of the voltage gauge in the control box, and it show 120 as well, so the gauge is good, he current percentage gauge bounces, -hertz gauge has never worked- . The convenience outlet has 120 on both plugs. And...