Found the S1 jumpers from both machines on the garage floor. Too many hours went into chasing down this stupid thing. Thank you everyone for your help.
Yes it has worked for the last two summers. After opening the switch up there is no physical connection between terminals 8/6 and 2/4. Installed a jumper between terminal 4 and 8 and everything is working as it should. Any way this is not a switch issue? Any recommendations on where to buy a...
Jumpering S1-2 to either S1-6 or 8 allows it to crank normally. I know this sounds like a stupid question but I should have continuity between all the even terminals on the S1, correct?
Attached are a couple photos of the switch. We have traced power through CB1, S17, S10, CR1, and MT4. Back to thinking it is the S1 switch. Swapped S1 with an old switch but didn't actually verify proper function.
MEP 803a. Fuel pumps run. Starter will not turn over using S1. Dead Crank operates normally. No power at terminal 7 on S1 when in start position. No voltage at starter solenoid post 2 when starting. No power at common posts 6 & 8 on S1. No voltage between pins F and J on diagnostic connection...