  1. Triple Jim

    MEP-016C load tested to 4100kW

    It's also convenient to remember it as P=V²/R. Since R is (nearly) constant in your test, power is proportional to the square of the voltage.
  2. Triple Jim

    MEP-016C load tested to 4100kW

    Good load test, thanks for the video. If the 4200W at the generator was measured at 120V, but your commercial power was 118.6V, that would account for the difference, assuming all the loads were resistive.