Steel Soldiers now has a few new forums, read more about it at: New Munitions Forums!
Microsoft MSN, Live, Hotmail, Outlook email users may not be receiving emails. We are working to resolve this issue. Please add support@steelsoldiers.com to your trusted contacts.
To do it simply, if you want to run your generator in 120 single phase only mode and you are not sure if the jumper was installed or not, when you run it in 120 only mode just put a jumper from L1 to L0 at the connection lugs. Just be sure to remove it when you change modes to something else.
No, you do not need to take it out each time you use the generator in a different configuration.
The Military didn't design it like this, someone in the military did however find that there was something wrong with the OEM set-up, hence the TB was issued to rectify the situation.
I have a...
Sure, ad-blocking software does a great job at blocking ads, but it also blocks useful features of our website like our supporting vendors. Their ads help keep Steel Soldiers going. Please consider disabling your ad blockers for the site. Thanks!