  1. Speddmon

    #LO to #6 jumper??

    To do it simply, if you want to run your generator in 120 single phase only mode and you are not sure if the jumper was installed or not, when you run it in 120 only mode just put a jumper from L1 to L0 at the connection lugs. Just be sure to remove it when you change modes to something else.
  2. Speddmon

    #LO to #6 jumper??

    You are correct, must be an issue from the crash/server change. I'll fix it, thanks.
  3. Speddmon

    #LO to #6 jumper??

    No, you do not need to take it out each time you use the generator in a different configuration. The Military didn't design it like this, someone in the military did however find that there was something wrong with the OEM set-up, hence the TB was issued to rectify the situation. I have a...