• Steel Soldiers now has a few new forums, read more about it at: New Munitions Forums!

  • Microsoft MSN, Live, Hotmail, Outlook email users may not be receiving emails. We are working to resolve this issue. Please add support@steelsoldiers.com to your trusted contacts.

Search results

  1. Keith_J

    Max amp draw on MEP-802A @ 240V

    The meter will read the real plus reactive current. Which means if there is a load of 6250 W that is pure resistive, the generator will be fine. But if you have a motor rated at 4000 W with a 0.60 power factor, it would exceed rated limits of the generator (6666 W) as there would be 2666 W of...
  2. Keith_J

    Max amp draw on MEP-802A @ 240V

    6240 watts real plus reactive, this means power factor of 0.80 so if you multiply 6240 by 0.80 you get about 5000 watts. Ok, more like 4992 but significant figures yada yada ymmv eieio ;)
Top
AdBlock Detected

We get it, advertisements are annoying!

Sure, ad-blocking software does a great job at blocking ads, but it also blocks useful features of our website like our supporting vendors. Their ads help keep Steel Soldiers going. Please consider disabling your ad blockers for the site. Thanks!

I've Disabled AdBlock
No Thanks