The meter will read the real plus reactive current. Which means if there is a load of 6250 W that is pure resistive, the generator will be fine. But if you have a motor rated at 4000 W with a 0.60 power factor, it would exceed rated limits of the generator (6666 W) as there would be 2666 W of...
6240 watts real plus reactive, this means power factor of 0.80 so if you multiply 6240 by 0.80 you get about 5000 watts. Ok, more like 4992 but significant figures yada yada ymmv eieio ;)