Steel Soldiers now has a few new forums, read more about it at: New Munitions Forums!
Microsoft MSN, Live, Hotmail, Outlook email users may not be receiving emails. We are working to resolve this issue. Please add support@steelsoldiers.com to your trusted contacts.
+1 on the grounding. In addition code requires a GFCI outlet or an approved inline GFCI cord to use a generator stand alone. I had to update the convenience outlet on my MEP-003 to GFCI.
The main question is this - Are you connecting the generator to an existing power distribution system that already has a ground system. If the answer to that question is YES then you wouldn't bond the neutral to ground at the generator but you would extend the existing system ground to the...