  1. DieselAddict

    MEP 120V Output, Balanced vs. Unbalanced

    +1 on the grounding. In addition code requires a GFCI outlet or an approved inline GFCI cord to use a generator stand alone. I had to update the convenience outlet on my MEP-003 to GFCI.
  2. DieselAddict

    MEP 120V Output, Balanced vs. Unbalanced

    The main question is this - Are you connecting the generator to an existing power distribution system that already has a ground system. If the answer to that question is YES then you wouldn't bond the neutral to ground at the generator but you would extend the existing system ground to the...
  3. DieselAddict

    MEP 120V Output, Balanced vs. Unbalanced

    No, only bad reasons. The neutral should be bonded to ground in a single location.