  1. D

    MEP 805B slow to close breaker

    I ended up pulling the contractor and found major arc damage on the left most contact load side. Replaced the contractor plates and lubricated the selinoid. Now works pretty. Still slow to close when cold ( less than 70f ) but once it has cycled a few times it is fine. Used 3 in one light...
  2. D

    MEP 805B slow to close breaker

    Had some nice weather today went out and checked the toggle switch, it tests ok. The K1 looks easy enough to get at, all the control leads are close to the case no easy way to get a meter in to them. with out taking it out of the set completely. I have played with it now, and it appears to only...
  3. D

    MEP 805B slow to close breaker

    if there is no logic check (IE freq good, volt in range) then basically it is just repeatedly trying the breaker close toggle switch (3 position on the control board) UP to close, neutral , Down to Open It will always open on first try, just not close the reaction time varies, i can hold the...
  4. D

    MEP 805B slow to close breaker

    The question then is what to check to find out why it takes so long, some kind of logic check, bad switch?
  5. D

    MEP 805B slow to close breaker

    Hi, another question on my 805b my assumption is it is it slow to close, i let the unit run for 5 mins no load, then go to close the output breaker, pushing the toggle to close and nothing happens for 3 - 5 mins adjusting the frequency and/or voltages do not make a difference holding the switch...