Have you used your load bank on other sets and do their %Load meters work OK?
Have you cleaned contacts 1-6 in P6 and J6?
The CT signals go thru those contacts.
If K8 was bad it may influence the %Load reading. You might try disconnecting the two wires on K8-2 and connect the two wire lugs...
A number of things come to mind
1) Gen head leads hooked to wrong TB3 terminals
2) Wrong leads from TB3 running thru the CT2
3) Wrong number of turns of wire thru CT2
4) Bad CT
5) other...