  1. D

    MEP-802a contactor

    The begining of this thread was about trying to overload the genset with resistive load. You cant get to the overload current trip point with resistive load only, period. 5.5 kw is the spec limit for kW load, nothing to do with reactive load, current load or overload. MIL DTL 53133 says to...
  2. D

    MEP-802a contactor

    Spec limits on Max power (kW) is 110% of rated kW on all TQG sets. Over load is current. So if you can get 5.5 kW then the set is operating as it was designed to.
  3. D

    MEP-802a contactor

    You cant increase the current that high using resistive load only or the engine will stall. You need reactive load to do that.
  4. D

    MEP-802a contactor

    (anything over 130% the trip time is inversely proportional to time.) I meant over 130%, trip current is inversely proportional to time.
  5. D

    MEP-802a contactor

    I hate to tell you but you now know nothing. The overload trip is over current if you use a resistive load bank then you would have to put to much resistive load on the set to get to the over current level. The over current trip point is 130% of rated current and the relay trips in 8 +/- 2...