  1. drgreg

    Generator Conductor to House Panel Question

    What is the gens. rating?
  2. drgreg

    Generator Conductor to House Panel Question

    You should have only 1 transfer switch feeding the building.
  3. drgreg

    Generator Conductor to House Panel Question

    You cannot fuse #8 at 60 amps.
  4. drgreg

    Generator Conductor to House Panel Question

    Conductors, Paralleled NEC 310.4 Minimum size 1/0 copper. # 6 THHN is good for 65 amps, per NEC T310.16 You should also size the wires by the nameplate rating of the generator. NEC 445.13 The wires should also be protected by an overcurrent device at the source.