    Single phase and three phase out of a mep006a

    Jim, the key to that statement is MOST 120/240V single phase equipment works fine on 120/208V 3 phase, without knowing more about the situation it is easy to give bad advice. Ike p.s. also in mixed environments such as this you have to be VERY careful on grounding, also there is concern about...
  2. I

    Single phase and three phase out of a mep006a

    The thing is NO GENERATOR will deliver both at the same time, the best you can do is add a step down transformer to supply your single phase load, but you need to make sure this will not eat into your available 3 phase too much. The problem being is you loose 2 - 3 times the 3 phase capacity as...
  3. I

    Single phase and three phase out of a mep006a

    You are never going to get true single phase and 3 phase out of the generator at the same time, the closest you can do is put a step down transformer on one or two of the legs, doing this will only allow you to draw a small fraction of the total output in single phase though (think of a...