    MEP-002A Left Connected when Main Power was Restored

    Yes, there should be two screws that run the full length of the switch that you want to just loosen, not remove. If your switch is stuck that should allow just enough slack to free the switch and allow you to spray contact cleaner throughout the length of the switch so it makes its way into the...
  2. C

    MEP-002A Left Connected when Main Power was Restored

    I'm wondering if the selector switch being stuck, which from your comments above, was not the case before the power restoration event is a symptom that's being overlooked. If that's the case, I would take off the side panel and just loosen the nuts on the wafer switch and spray contact cleaner...
  3. C

    MEP-002A Left Connected when Main Power was Restored

    Also, if you are isolating your generator from house or barn make sure it is grounded once isolated. Once disconnected from your panel's gnd it becomes a "Self Derived System" and needs to be independently grounded via it's own driven ground rod. There is also the requirement to bond/unbond...