Steel Soldiers now has a few new forums, read more about it at: New Munitions Forums!
Microsoft MSN, Live, Hotmail, Outlook email users may not be receiving emails. We are working to resolve this issue. Please add support@steelsoldiers.com to your trusted contacts.
For the circuit box, unless it is an interlock that only allows one either the main breaker, or the generator feed breaker to be closed, not both. Without some sort of a physical lock of some type that only allows either the gen or the utility to be connected at the time it isn't legal. Just...
I came up with another reason why using a 3k on 240 wired to the house might be a bad idea.
Load balancing.
In 120V only mode, you have 3kw of power through that one circuit.
In 120/240 mode, that 120V power is now separated into 2 1500 watt circuits.
So to use my example above with hair dryer...
Get either a generator interlock kit installed, or a sub panel for generator use.
What others posted, saying that you can kill linemen if wired incorrectly, is 100% true. Linemen HAVE been killed by homeowners incorrectly wiring in generators. Backfeeding it into the house through a dryer...
Sure, ad-blocking software does a great job at blocking ads, but it also blocks useful features of our website like our supporting vendors. Their ads help keep Steel Soldiers going. Please consider disabling your ad blockers for the site. Thanks!