Sure, with a 22kw generator in place.
For a MEP-803A 10kw, not so much.
Cost prohibitive.
Each shedding breaker is not cheap. You will have to widdle your entire panel down to 10kw.
A generator break out box with only the necessary breakers could be done.
Have you priced out a 200 amp...
Howdy,
So far, by what you have stated. You are way in over your head.
You do not want to use a ATS with a 200 amp service and a MEP-803A generator.
ATS = automatic transfer switch
By standards, you would need a generator to fully support your 200 amp panel. That means a 200 amp output.
Load...