Where the nest it was OK.
The L1 line was chewed and was touching the case. I found it checking continuity from L1 to Ground.
I had to remove the bond when checking all the continuity points. Then I put it back when I found the issue.
So .. a few weeks back I...
The phase-3 vs phase-1 problem was me, I didn't know the phase-3 and phase-1 controlling was the one behind the panel, VS the switch that is on the panel and lets you select phase-1 and phase-3.
THanks for your help on that !
Now when I put the switch (behind the panel) on Phase-3 is shows...
The switch I am referring to is the one that selects the Phase and legs you want to use. (sorry i don't know it's name).
I did look thought he TM's but I didn't see anything that popped out at me.
It is this one circled here. (not my gen just example of the switch).
Without the load hooked up the Phase 1 shows no voltage.
Without the load hooked up on any the phase 3 setting the gen runs ok and produces power on the phase 3 settings.
With the load hooked up the short-circuit light come on as soon as the gen circuit is turned on.
I'll go through the TM's...
Could someone please help me on where I should I look to correct his problem?
Generator engine MEP802A starts and run fine.
With the switch on any of the Phase 3 settings the meter on the unit shows the generator has power, and myself with a multi meter shows it has power BUT when a load is...