    MEP-701A MEP-016b Voltage Selector/Ground Question

    Isaac, You bring up a very good point of knowing how the machine is configured before it is run. Interesting that your 701A was set up as you described, which may actually be in accordance with the manual. I have only had a few 016Ds to play with and they seem to follow the the same...
  2. ETN550

    MEP-701A MEP-016b Voltage Selector/Ground Question

    Ignore what is going on behind the curtain! If your particular reconnection switch setting does not utilize a certain lug such as L3 for output then don't worry if there is voltage at that particular lug. It will not be connected to anything. The voltage reconnection switch is complicated and...
  3. ETN550

    MEP-701A MEP-016b Voltage Selector/Ground Question

    What you are posting above makes sense if L3 and L0 are connected internally by the reconnection switch. The generator is a 3 coil, 6 lead machine. In the 240 single phase mode the coils are in a zig zag configuration and L0 is connected to the T4/T2 junction on the 240 volt diagram fig 4.1 pg...