    802a no power at lugs

    Which motor mount is missing? One of the forward mounts towards the radiator fan? Just an FYI incase you aren't familiar, these machines only use the 2 forward mounts and the mounts on the generator head, they don't use any mounts at the 2 rearward tabs on the side of the block near the bellhousing.
  2. R

    802a no power at lugs

    If you haven't done so already you need to test the circuit to see where it's broken. Start it up and first verify you have 24V on the X terminal of K1 If so, follow the instructions in the TM, it will tell you to manually connect the Y terminal to ground with a jumper. If K1 is good it should...
  3. R

    802a no power at lugs

    Not sure if you tested the green AC circuit interruptor bulb, but assuming it's good and you don't have voltage at the lugs, the TM will tell you how to test both the interruptor as well as the power and ground wires that activate it. If all the tests pass but the interruptor still won't close...