• Steel Soldiers now has a few new forums, read more about it at: New Munitions Forums!

  • Microsoft MSN, Live, Hotmail, Outlook email users may not be receiving emails. We are working to resolve this issue. Please add support@steelsoldiers.com to your trusted contacts.

 

Search results

  1. D

    MEP 003a Question

    I was surprised the electrician used wire nuts, but he said it was fine. He was there to wire a garage sub panel (that had a permit pulled and had to be inspected) and he seems to know the code pretty well. To OP of this thread, did you check out MEP-003 hook up sticky in aux equipment forum...
  2. D

    MEP 003a Question

    The ground from your 8/4 goes to ground lug on generator. Did not follow all of question 2, but ground from 8/4 goes from gen ground lug to ground inlet in the 4 prong plug you have set up for interlock. The 4 prong plug is hooked to panel the same way you would hook up any 240V plug. When I...
  3. D

    MEP 003a Question

    As has been said before, you probably need to get an electrician in for at least a consultation. I know it costs, but you sound a little in over your head, and even if you get great generator and hook up advice here, no one can see if you missed something. An 003 makes enough juice to kill...
  4. D

    MEP 003a Question

    Typically, they are neutral bonded. Easy enough to unbolt the bonding wire from back of chassis ground lug.
Top
AdBlock Detected

We get it, advertisements are annoying!

Sure, ad-blocking software does a great job at blocking ads, but it also blocks useful features of our website like our supporting vendors. Their ads help keep Steel Soldiers going. Please consider disabling your ad blockers for the site. Thanks!

I've Disabled AdBlock
No Thanks