I was surprised the electrician used wire nuts, but he said it was fine. He was there to wire a garage sub panel (that had a permit pulled and had to be inspected) and he seems to know the code pretty well.
To OP of this thread, did you check out MEP-003 hook up sticky in aux equipment forum...
The ground from your 8/4 goes to ground lug on generator. Did not follow all of question 2, but ground from 8/4 goes from gen ground lug to ground inlet in the 4 prong plug you have set up for interlock. The 4 prong plug is hooked to panel the same way you would hook up any 240V plug.
When I...
As has been said before, you probably need to get an electrician in for at least a consultation. I know it costs, but you sound a little in over your head, and even if you get great generator and hook up advice here, no one can see if you missed something. An 003 makes enough juice to kill...