Steel Soldiers now has a few new forums, read more about it at: New Munitions Forums!
Microsoft MSN, Live, Hotmail, Outlook email users may not be receiving emails. We are working to resolve this issue. Please add support@steelsoldiers.com to your trusted contacts.
Keep in mind sometimes local laws might be different.
The neutral bonding strap needs to be removed IF anywhere else in the system is also neutral bonded.
In the case of a house this is almost always the case in your main panel, you can take a pic of the inside of your panel and we could...
That should be fine just hooking 1 hot to L1 though I would probably do L3 myself.
FYI if you set the generator into 120V mode it sends everything to L3.
So if you did hook to L1 and put the set in 120V only you would get nothing.
Sure, ad-blocking software does a great job at blocking ads, but it also blocks useful features of our website like our supporting vendors. Their ads help keep Steel Soldiers going. Please consider disabling your ad blockers for the site. Thanks!