    MEP 802a - split phase connection

    Keep in mind sometimes local laws might be different. The neutral bonding strap needs to be removed IF anywhere else in the system is also neutral bonded. In the case of a house this is almost always the case in your main panel, you can take a pic of the inside of your panel and we could...
  2. nextalcupfan

    MEP 802a - split phase connection

    That should be fine just hooking 1 hot to L1 though I would probably do L3 myself. FYI if you set the generator into 120V mode it sends everything to L3. So if you did hook to L1 and put the set in 120V only you would get nothing.