I have a MEP 003A that the output voltage is not stable. Most times when started the voltage is 120/240 as it should be. Occasionally when started the voltage goes to 150/300 and stays there. When I shut the generator down and restart it sometimes the voltage goes right back to 300+ and sometimes is goes to 120/240. When output is 120/240 the voltage is stable regardless of load and the voltage adjust "pot" adjusts from around 210-260 as it should. When the voltage is 150/300 the voltage adjust "pot" will adjust voltage from around 280-320. I have cleaned and tested all grounds. I loosened and retightened all connections on the voltage regulator board. I have replaced T2. The voltage adjust "pot" reads from 0-1000 ohms as it should. The voltage regulator board "looks" OK. There is no goo coming out of the caps and nothing looks burned. I do not have a spare voltage regulator board. If I did I would swap it out. Intermittent problems are (for me) the hardest to find and fix. Does anybody have any suggestions? Thanks............