MEP002A No Power Output and Guages Not Working

mkcoen

Well-known member
Steel Soldiers Supporter
5,637
380
83
Location
Spring Branch, TX
A couple of years ago I bought a MEP002A for my inlaws. They picked it up and it's been sitting in their driveway getting started once a month but nothing else. FIL decided to hook it up to the house this weekend and said he was getting power to the accessory plugs and then shut the generator down, wired it to the house and now is getting nothing. He also waited until now to tell me the gauges aren't working (they were when I tested it). I told him to undo the house connection and start it back up to see if there's something in that but haven't heard back yet.

Is there anything that will trip a switch to kill the power output with the generator still running? I told him to check the CBs by the accessory plugs and he said they were up so shouldn't be that. What about the gauges? They were working fine here in TX but now that it's in the 4 Corners area of NM they're not (and not like I can just run over and check).
 

Chainbreaker

Well-known member
1,740
1,810
113
Location
Oregon
I would also have him drop the front panel and take a quick look inside the control box. Anything appear burnt (paying close attention to the AC VR board), or loose or disconnected?

Also, another simple thing to verify: Is the AC Output Reconnection Switch turned to far right and set to 120/240?
 

mkcoen

Well-known member
Steel Soldiers Supporter
5,637
380
83
Location
Spring Branch, TX
I would also have him drop the front panel and take a quick look inside the control box. Anything appear burnt (paying close attention to the AC VR board), or loose or disconnected?

Also, another simple thing to verify: Is the AC Output Reconnection Switch turned to far right and set to 120/240?
I had him check those and walked him through the switch. I actually had him switch it back and forth a couple of times just in the off chance there might be some corrosion in there. I'm guessing I'm in for a road trip around Thanksgiving to either figure it out or bring it home. I've got a spare MEP002 that I've been using for parts for my MEP003 and I'm sure there's enough good stuff left that I can swipe (like gauges and such) to get it running here. It's tough trying to diagnose something over the phone (or on a web forum) when you can't physically touch it or know what it's doing at a certain time.
 

87Nassaublue

New member
116
0
0
Location
Sharpsburg, Ga
How much does he know about electronics, wiring and these units? How much load did he put on the unit or what all did he try to power at once? We really need more information to help. An 002a is only 5kw. In the grand scheme of things, that's not a lot of power to run a house with AC, kitchen appliances, lights, etc. Something obviously went wrong. I would suggest, disconnecting the unit from the house and then checking the unit out. I'd also recommend after you have the generator putting out again to do a load test. I heard of someone overloading an 016 and took out the VR.
 

mkcoen

Well-known member
Steel Soldiers Supporter
5,637
380
83
Location
Spring Branch, TX
How much does he know about electronics, wiring and these units? How much load did he put on the unit or what all did he try to power at once? We really need more information to help. An 002a is only 5kw. In the grand scheme of things, that's not a lot of power to run a house with AC, kitchen appliances, lights, etc. Something obviously went wrong. I would suggest, disconnecting the unit from the house and then checking the unit out. I'd also recommend after you have the generator putting out again to do a load test. I heard of someone overloading an 016 and took out the VR.
Never actually had it hooked to the house just to the disconnect box and nothing was working. He knows more about household electricity than I do (a LOT more) but almost nothing about the MEPs. I walked him through basic operations when he picked the unit up 2 years ago and provided copies of all the manuals but that's been a while. First thing I recommended was undoing whatever he had done and trying the generator again. I haven't heard back so don't know if he didn't get around to it or it didn't work.
 

jamawieb

Well-known member
1,405
491
83
Location
Ripley/TN
If he doesn't have anything registering on the meters, then it's more than likely in the distribution box. It's either the exciter, linear reactor, or CVT1. If you have an extra distribution box, just take it with you because it may take to long to test all the items I listed in a short amount time. More than likely it was nothing that he did but when they are not used much and then you put a large load on them, things go bad with old electronics.
 

87Nassaublue

New member
116
0
0
Location
Sharpsburg, Ga
Hmm, sounds like he couldn't have hurt it if he didn't try to pull any power from it yet. It sounds like it's time to break out the TM and the schematics and start tracking down the cause of some of the symptoms. I had a simple power feed connection that took down a 016D. Keep us posted on the progress. Its sounds interesting.
 