If you are running this to your house, you must run a ground to the house, 4 wires total. That box has the ground and neutral bonded, going to the same block with just the single neutral returning to the panel(bare wire and coated wire going to block on the bottom left). I don't think that is the correct setup. The neutral and ground should go directly to the panel and stay separated until they get there, where in the panel bonds the two.
I believe you should also put a ground rod in at the generator, attached to the ground terminal, and remove the bonding bar between L0 and GND
FWIW, I'm running 3 legs 4awg copper(Hot-Hot-Neutral) and 1 leg 6awg for the ground THWN in conduit.
I believe you should also put a ground rod in at the generator, attached to the ground terminal, and remove the bonding bar between L0 and GND
FWIW, I'm running 3 legs 4awg copper(Hot-Hot-Neutral) and 1 leg 6awg for the ground THWN in conduit.