TheEquineFencer
Member
- 38
- 10
- 8
- Location
- 27828
I have a MEP-804A generator I'm trying to help a guy out with. It's connected 120/208. The symptoms are no AC output. I've noticed as long as the start switch is held, it has AC output, release it and it goes away. So I know the start disconnect circuit works along with the generator end itself. It's a control issue. So what's not picking up? Which terminals on the Voltage regulator should I have DC input to to hold it active?I'd love to know what each terminal on thr voltage regulator does what?