Hello everyone, I am new to this community and am grateful to have this forum for help. My newly acquired genset has 289 hours on the hour meter and the engine seems to run well. I have changed all the fluids and filters. I have downloaded the manuals and have tried to follow them the best I can. The genset does have a 3 amp fuse on the voltage regulator but does not have a MOV installed, one is on order. I have a few questions:
1- The AC volt meter and AC ammeter do not work on every AM-VM setting. When the AM-VM is set to 3 phase power, the volt meter seems to work. I traced the wires using the wire schematic and replaced the AM-VM switch without any change.
2- In single phase power my DMM shows an output voltage of 177-210 at the output lugs. I have taken measurements at the voltage regulator using the testing procedure (2-27.2) and are as follows:
120/240: voltage range is 177-210
step h: 7.5 VDC
step j: 87.5 VAC
step l: 119.6 VAC
step n: 4550 ohms
When doing Quad Circuit testing:
Terminal 1 and 2: 1.2 VAC
Terminal 3 and 4: 102.2 VAC
Terminal 5 and 6: 4.2 DC
Terminal 7 and 8: 74.6 VAC
I purchased this generator because I thought I could use the manuals to make any repairs that it needed but I am over my head and any help would be greatly appreciated. I have contacted 3 different diesel generator repair shops in my area without any response. Does this genset sound repairable?
Thank you
1- The AC volt meter and AC ammeter do not work on every AM-VM setting. When the AM-VM is set to 3 phase power, the volt meter seems to work. I traced the wires using the wire schematic and replaced the AM-VM switch without any change.
2- In single phase power my DMM shows an output voltage of 177-210 at the output lugs. I have taken measurements at the voltage regulator using the testing procedure (2-27.2) and are as follows:
120/240: voltage range is 177-210
step h: 7.5 VDC
step j: 87.5 VAC
step l: 119.6 VAC
step n: 4550 ohms
When doing Quad Circuit testing:
Terminal 1 and 2: 1.2 VAC
Terminal 3 and 4: 102.2 VAC
Terminal 5 and 6: 4.2 DC
Terminal 7 and 8: 74.6 VAC
I purchased this generator because I thought I could use the manuals to make any repairs that it needed but I am over my head and any help would be greatly appreciated. I have contacted 3 different diesel generator repair shops in my area without any response. Does this genset sound repairable?
Thank you