I am troubleshooting a MEP-804A which has what seems to be a common issue: While it is held in START the voltage goes up to 230VAC
but as soon as it is released it drops to about 24VAC.
I have been doing some of the steps that are mentioned in the -24 manual and in various threads here.
The voltage regulator in this one is a 122-3054 P/N 30554SOCN88-22560
The manual lists 2 options none of which is this one: P/N 01- 21501-1 & P/N 01- 21501-2
I have done the measurement of the disconnected wires from Pins 1 & 3 of the regulator at 34 ohms.
The voltage pot test is 3K CCW and 13.5K CW
If someone can lend some clarity to the VR P/N confusion or suggest some tests that would be very helpful.
Thanks.