Ok will try that thank you. I have also noticed that the copper tie bar was cut at the top right hand corner between I believe T11 and T12.
Does that mean it was originally at 240/416 and converted to 120/208? There was also a jumper that connected ( I believe T12 and T2).
I have the MEP006A diesel generator currently set at 120/208 V and would like to convert it to 240/416 V.
Looked and the TM but couldn't find any detail instructions on how to do this. The generator is to be used to
operate equipment that require 3 phase 380 volts. The volt meter only gets up to...
I have the MEP006A diesel generator currently set at 120/208 V and would like to convert it to 240/416 V.
Looked and the TM but couldn't find any detail instructions on how to do this. The generator is to be used to
operate equipment that require 3 phase 380 volts. The generator currently only...