• Steel Soldiers now has a few new forums, read more about it at: New Munitions Forums!

  • Microsoft MSN, Live, Hotmail, Outlook email users may not be receiving emails. We are working to resolve this issue. Please add support@steelsoldiers.com to your trusted contacts.

Search results

  1. A

    MEP006A Voltage Conversion

    Ok will try that thank you. I have also noticed that the copper tie bar was cut at the top right hand corner between I believe T11 and T12. Does that mean it was originally at 240/416 and converted to 120/208? There was also a jumper that connected ( I believe T12 and T2).
  2. A

    MEP006A Voltage Conversion

    I have the MEP006A diesel generator currently set at 120/208 V and would like to convert it to 240/416 V. Looked and the TM but couldn't find any detail instructions on how to do this. The generator is to be used to operate equipment that require 3 phase 380 volts. The volt meter only gets up to...
  3. A

    Mel-006a

    I have the MEP006A diesel generator currently set at 120/208 V and would like to convert it to 240/416 V. Looked and the TM but couldn't find any detail instructions on how to do this. The generator is to be used to operate equipment that require 3 phase 380 volts. The generator currently only...
Top