    MEP-803A mixed load test results

    Zed, I tried that, don't think this is a calibration issue with the meter. There is not near enough adjustment to get it close to accurate. With the adjustment I can get it to go from 30% on meter to 50% on the meter but no higher at 10kw load. I removed the leads to the ammeter and cleaned...
  2. W

    MEP-803A mixed load test results

    I finished the load bank today which is 4 220V 2500W hot water tank elements and 2 120V 1500W elements in a 55 gallon drum. After a warm up I applied different loads and the Gen handled them fine up to 13k. I let it run about 15 minutes on 10k watts and other than quite a bit of smoke, least...
  3. W

    Ok this is probably going to be a really dumb question or two

    But. My new MEP 803A when I purchased it the seller had sent me pics of it and had 47 hours on the clock. As part of the prep work for the install I ordered a 24V maint charger for it. When the very nice seller and I were talking about the possible purchase I had done my due diligence and I...
  4. W

    Hello All, New member here

    My plan is to leave that bottom cap off and only put it on when the gen is run. That way if there is moisture in the pipe or if say the flapper would get stuck open I will know it as I will see the drips on the floor. The exhaust upright and the short 6" pipe that goes in to the flex fitting...
  5. W

    Hello All, New member here

    That sounds good to me. Going to send you a PM as I have a question not Gen related.
  6. W

    Hello All, New member here

    I took a look and mine does have the excite circuit fuse installed but there is not a varister between #7 and #8? Should it have one?
  7. W

    Hello All, New member here

    Brian, Yep you are close, picked up my Grasshopper out your way, well in Belleview. Quad fuse mod.....hmm will look that up. I saw that they had a bunch of units coming up for auction in PA when I was looking. I thought about it but I just don't have the time so went the easy but more...
  8. W

    Hello All, New member here

    Pictures as promised. The gen on the 6 wheel sled. The exhaust stack, it is 1.25" pipe all the way up and out. Made up a simple steel bracket that the pipe goes through and on top of the bracket there is a heavy steel clamp I made that bolts around the pipe and rests on top of the...
  9. W

    Hello All, New member here

    Yes it takes away a real worry. I have a small back up gas gen and a 3/4 HP regenerative blower I was using for power failures but the amount of air it pushes is just barely enough to keep the fish from gulping at the surface. There is something to be said for peace of mind:) Not to mention...
  10. W

    Hello All, New member here

    I will post pics tomorrow after the exhaust install. Even with the posts here I still was not convinced the 803 would be enough to run everything but it appears to be with room to spare. The house is all electric except for the stove which is propane. Have two AC units a 3 or 4 ton? Don't...
  11. W

    Hello All, New member here

    Hello, I'm Wills, not Willis, everyone sees that extra I till I point out it isn't there. Just wanted to introduce myself though I have been reading threads here for a week or so so feel like I already know some of the regular posters. I know I will need some help sooner or later. I own a...