  1. Keith_J

    MEP 002A and 003A

    Generators work by spinning a magnet inside a coil(s). These generators use an electromagnet and the electricity for this magnet comes from the voltage regulator. So running a set at lower than rated speed causes the regulator to max out. This burns the output transistor. Yes, I simplified...
  2. Keith_J

    MEP 002A and 003A

    Another issue not addressed in the TMs or LOs is oil level with respect to listed quantities. These engines have oil coolers which have a thermostat, the TM states oil is to be changed while engine is hot. Not specified is why, the hot oil lets the oil cooling system drain fully. Likewise...
  3. Keith_J

    MEP 002A and 003A

    The maximum current in three phase should be 17.3 amperes. Running 3 circuits to L0 for 120 volts results in 2076 watts per leg for a total of 6228 watts. At PF of 0.8, that is 5 kw. Running 3-phase, that would be 3 legs of 208 volts at 17.3 amps gives 3598 watts, the factor of the square...