  1. D

    MEP004A Constant 200V

    I've had it on the back burner. Hopefully have time this winter.
  2. D

    MEP004A Constant 200V

    You sir, are an encyclopedia! Thank you!
  3. D

    MEP004A Constant 200V

    Not specifically what -24P means, but reading through the TM it seems to be the parts diagram. The other TMs are operational and shop manuals. Am I correct? Thanks
  4. D

    MEP004A Constant 200V

    Sorry, I thought I had downloaded all of the TMs. This one wasn't on the list. I found what you referred to exactly where you said. Thank You!
  5. D

    MEP004A Constant 200V

    I am trying to find the NSN for the transformers in the static exciter board. I have the numbers on the parts themselves, but don't seem to be in proper format. I also thought the TM would have some specs for the transformers. I'm at a hurdle. In TM 9-6115-464-34, page 3-271, item #'s 24,36,45...
  6. D

    MEP 831a fuel pump working, not going through injector pump.

    Thank you. I'm certainly in the dark on this.
  7. D

    MEP004A Constant 200V

    Yes, I didn't check resistance. That's the reading I got with the base as cathode. The part # being 1N1009R, I found to be a reverse diode. I did not remove them, which I could. Do I need to re coat the parts with anything when I'm done? Thank you much Doug
  8. D

    MEP004A Constant 200V

    I did check the diodes and all 6 came in at an average of .42 for continuity. Having pierced the coating to make contact, do I need to re-coat or repair the coating? As I read the TM test procedure for the windings, I don't have the equipment, just a DMM. I will check the other transformers in...
  9. D

    MEP 831a fuel pump working, not going through injector pump.

    You Sir, are a fountain on knowledge! I could only hope to ever gain a portion of your knowledge and insight that you've displayed. Thank you! K15 - No light L0-L1 = 0v L0-L2 = 0v CR2 = 27v S1-4 = 27v S1-5 = 27v S19-2 = 27v S19-1 = 27v CB1 = 27v both terminals Battery, engine running = 27v...
  10. D

    MEP 831a fuel pump working, not going through injector pump.

    Set running Measure voltage @A5. - A,B,C A&B 181.5V B&C. 181.5V A&C. 181.5V Battery is quite old. I do measure 27.4vdc at battery, unit running. The other higher dc voltage doesn't make sense to me either. For example, the hour meter doesn't run, but gets 40v on one terminal, 21 at the other...
  11. D

    MEP 831a fuel pump working, not going through injector pump.

    K12-12= .011v K12-4. =.011v K15-12=.001v K15-8. =12.36v S7-8. =40.94v S5-5. =41.02v S5-6. =.014v S5-4. =41.03v S5-1. =40.8v S5-2. =26.25v A5-A=100v A5-B=100v A5-C=160v Thank you for your time! Doug
  12. D

    MEP 831a fuel pump working, not going through injector pump.

    K12 - no LED Voltmeter shows 160
  13. D

    MEP004A Constant 200V

    😂😂😂 I'll dig into the exciters and diodes. The transformer that was over 400 deg was concerning to me, purely from a logic standpoint.
  14. D

    MEP004A Constant 200V

    Are those temperatures abnormal?
  15. D

    MEP 831a fuel pump working, not going through injector pump.

    RPMs adjusted. 182 at A-B, B-C. When closing circuit, K1 contactor not closing. Switch S5 seems to function ok by continuity check. Trying to follow schematic to figure out why contactor not closing.
  16. D

    MEP 831a fuel pump working, not going through injector pump.

    AH! Thank you! I have lost the factory spring on the gov. Made one up from a carb spring. It holds the rpm (albeit too low) but factory is better. Suggestion for the best source? Yanmar local dealer or good online source? Just looking for your two cents. Thank you! Doug
  17. D

    MEP004A Constant 200V

    I was testing some voltages this afternoon and checking some temperatures. The unit was running for approximately 10 minutes when the thermal temp was taken. My question is, is this cause or effect? On the larger trans. I got the following volt readings- H1 - 179V H2 - 181V X1 - 30.3V X2 -...
  18. D

    MEP004A Constant 200V

    I'm going to have to show my ignorance at to where the static exciter or bobbins are. I was looking through the TM and cannot locate a decent image or schematic.
  19. D

    MEP 831a fuel pump working, not going through injector pump.

    Should I start a new thread as the subject has changed?
  20. D

    MEP 831a fuel pump working, not going through injector pump.

    A&B - 136v B&C -136v Voltmeter shows 120v Terminals on back measure 40v Nothing at convenience outlet J17 on J7/P7 plug burnt. Added connection through fire wall. Wire 1D16 136v between TB6 1-2-3. Unaffected by pot S1 although, only 75v when grounded to chassis.