  1. G

    mep-005a giving me a reverse power warning.

    Ya thanks scooby is 1.45 hours south of me small world lol I think a good friend of mine is going to work in his department to lol and ya it would be vary hard for line power to meet gen power have a ats and 3 breakers that all would have to be closed at the same time for that to happen
  2. G

    mep-005a giving me a reverse power warning.

    Thanks a wealth of knowledge as always does the k15 relay trip if say by some crazy event power were to be fed from the house? That's the only reason I would order a new one they are a bit pricy.
  3. G

    mep-005a giving me a reverse power warning.

    so i reread this and i think your saying that my fault should not be in the a9 IF i cant close the breaker which i cant. so issue lies elsewhere?
  4. G

    mep-005a giving me a reverse power warning.

    is there a way to test the a9 fault indicator system? and what component usually fails? the light only comes on when i close the breaker and will reset wehn i hold the reset switch but will come back as soon as i close the breaker.
  5. G

    mep-005a giving me a reverse power warning.

    Lol it's fine it gave me a place to start and find the correct manuals
  6. G

    mep-005a giving me a reverse power warning.

    Hey guy long time no talk lol was wondering when you'd chime in ya it will let you close the breaker if the battle short is on me and Scooby Shep bypass3d it by moving the lead from 7 on k15 to 8 now it will let me close the breaker without using the battle short the idiot light is on but...
  7. G

    mep-005a giving me a reverse power warning.

    So this morning I tried removing the wire from pin 8 and pin 1 not at the same time but still Same result I figured out that not always but sometimes I can put it in battle short close the breaker reset thebwarnign light and turn off battle short and it will stay running with breaker closed and...
  8. G

    mep-005a giving me a reverse power warning.

    K14 has Pin 1 x9v18c Pin2 x12f18n Pin 3 p58818 Pin 4 p5cx18 Pin 5 Pin 6 Pin 7 p206d18 Pin 8 p200v18
  9. G

    mep-005a giving me a reverse power warning.

    p62h18 goes to pin 6 on the overload protection device P61A18 goes to pin 8 on k15 revers power relay
  10. G

    mep-005a giving me a reverse power warning.

    Ok yes I checked the correct one and have 0 also mine has nothing connected to those 2 terminals also checked both to ground and with light on and off all results were 0
  11. G

    mep-005a giving me a reverse power warning.

    That is zero as well also checked both to ground same and same with light on and off also there’s nothing connected to those terminals k14 the over voltage relay correct?
  12. G

    mep-005a giving me a reverse power warning.

    My bad checking now
  13. G

    mep-005a giving me a reverse power warning.

    Yes while running and dc on meter k14 5 and 4 0vdc 4 to ground 27vdc 5 to ground 0 Vdc this is the same with light on or off
  14. G

    mep-005a giving me a reverse power warning.

    Also 0 for both
  15. G

    mep-005a giving me a reverse power warning.

    yes i have 0 volts rather the reverse power light is on or off
  16. G

    mep-005a giving me a reverse power warning.

    what do you want the video of?
  17. G

    mep-005a giving me a reverse power warning.

    Yes I have 0 volts between 8 and 7 while running and the reverse current light is on and off
  18. G

    mep-005a giving me a reverse power warning.

    ok so just took readings while it was running and reverse power light is on pins 3 and 8 read 27 volts dc 1 and 2 read 5.5 volts ac 8and 2 and 8 and 1 both read 7 vdc.
  19. G

    mep-005a giving me a reverse power warning.

    Ok Re read this so when it’s deenergized the nc position is default so to allow sc power to pass to the breaker so the relay is energized by something else telling it to or it’s stuck in that position considering it does this every time I hit the close breaker and will reset with the reset...