• Steel Soldiers now has a few new forums, read more about it at: New Munitions Forums!

  • Microsoft MSN, Live, Hotmail, Outlook email users may not be receiving emails. We are working to resolve this issue. Please add support@steelsoldiers.com to your trusted contacts.

MEP004 low voltage

peapvp

Well-known member
Steel Soldiers Supporter
1,108
1,223
113
Location
Basehor, KS
For beginners,

I would check R2 and S5 and R31

A11 CT 4,5,6 R2 AC Circuit Complete.jpg

The next question would be:

Was this Generator converted to Single Phase (@sewerzuk) ?

If so, make sure you adjust R2 Voltage Adjust Rheostat to 208 VAC across the two phases ( L1 and L3) and not 240 VAC or higher!

The A11, repaired or original, was designed for 208 VAC

When you adjust to 240 VAC then J13 M and L are too high. T2 Primary connects here and 240 on primary will put out 138 VAC on secondary.

Further, CT4 CT5 and CT6 are going to be in a imbalanced state after swerzuk's conversion.

All three CT's are connected to a Three Phase Transformer T1 and directly to CR 1, 2, 3, 4, 5 and 6, which form the Boost Circuit with Q5 and VR3 on the Voltage Regulator Board inside the A11
 

peapvp

Well-known member
Steel Soldiers Supporter
1,108
1,223
113
Location
Basehor, KS
@catienla

Mike, you need to post of what you are emailing me here as well. Otherwise, everyone is in the dark and we cannot help you.

Mike wrote via e-mail as he had e-mailed me before he posted this thread:

Mike:
Tried to run MEP004. It is only producing 87.5 volts on all 3 phases. Is there a way to adjust the voltage higher? When I ran it after last repair I measured 25

My Answer
Voltage Adjust Rheostat on front panel. Is this Genset converted to 1 Phase?


Mike's Answer
Thanks for your reply. Genset is not converted, using L1 and L3 for 220v. Rheostat doesn't change voltage on panel meter. Maybe I should have turned it and checked with a meter.
 

catienla

Member
52
43
18
Location
anawalt,wv
I think sometimes my mind is my worst enemy. I have been running this unit on two leads voltage at 220 vac since 2011, maybe this is why all my problems started. I knew it was 208 v but it did not register. When it produced 220-230 v this is what I used. I think I created my own problems. I'll check the circuits Peter listed and reply. Thanks to everyone for your help. I need it.
 
Top
AdBlock Detected

We get it, advertisements are annoying!

Sure, ad-blocking software does a great job at blocking ads, but it also blocks useful features of our website like our supporting vendors. Their ads help keep Steel Soldiers going. Please consider disabling your ad blockers for the site. Thanks!

I've Disabled AdBlock
No Thanks