Joe,
I removed both the voltage regulator/exciter and the control box. I took a look into both items and could not find and visible problems. As for the Terminal Board 101, I found it. With the control box out of the genset, I cannot check for 24v but I did check continuity between J2-terminal-R and lug number 11 and it was good, no open wire.
I can actually check continuity from J2-terminal-R all the way through to the test fault plug terminal-A where I am suposed to have 24v wich I have contunity, BUT my intial check for voltage did not have 24v. That tells me the problem is from the plug in J2 plug back to the s2 switch, because I had 24v on lug 3 on S2. Can we check to make sure that the wire from lug 3 on S2 goes directly to terminal 11 on terminal board 101?
Does this sound correct and make any sense?
Thanks,
Josh
I removed both the voltage regulator/exciter and the control box. I took a look into both items and could not find and visible problems. As for the Terminal Board 101, I found it. With the control box out of the genset, I cannot check for 24v but I did check continuity between J2-terminal-R and lug number 11 and it was good, no open wire.
I can actually check continuity from J2-terminal-R all the way through to the test fault plug terminal-A where I am suposed to have 24v wich I have contunity, BUT my intial check for voltage did not have 24v. That tells me the problem is from the plug in J2 plug back to the s2 switch, because I had 24v on lug 3 on S2. Can we check to make sure that the wire from lug 3 on S2 goes directly to terminal 11 on terminal board 101?