  1. Triple Jim

    NOCO Charger Question - MEP-803A w/Optima Red Tops

    The terminal voltage of an unloaded battery might tell you the percent charge, but that's the percentage of its capacity in its current condition. A failing battery can appear to be 100% charged, but not be able to supply the current needed to start an engine.
  2. Triple Jim

    Main power indicator

    Maybe it's because I live in such a sparsely populated area, but they seem to notify me very soon after the power returns.
  3. Triple Jim

    Main power indicator

    I have a Powerback alarm, but now my power company sends me a text message when the power returns.
  4. Triple Jim

    Mep-002A Bridge rectifier R1 burnt

    If the regulator is sending excessive control current to CVT1, which is one mode of failure, then it could, as you say, be the problem. If this is the case, if you disconnect the wire from terminal 17 of the regulator and tape its end so it doesn't contact anything, you will prevent the...
  5. Triple Jim

    Mep-002A Bridge rectifier R1 burnt

    This resistor is responsible for flashing the field during starting. It is connected to terminals 5 and 6 of board A4. During cranking the exciter field gets 24v from the master switch through diode CR2. The other end of the exciter field at terminal 5 is grounded through the resistor, via...
  6. Triple Jim

    Mep-002A Bridge rectifier R1 burnt

    Ray is correct that resistor is supplied by the 24v battery, not the regulator. As he said, it should carry current only when the switch is in the start position. Either you're right that the exciter filed resistance is very low, or for some reason it was carrying current to the exciter field...
  7. Triple Jim

    MEP 002a voltage adjust issue

    Yes, of course. I just said that if you're in doubt, you can check its accuracy.
  8. Triple Jim

    MEP 002a voltage adjust issue

    You can check a Kill-A-Watt meter against a meter that's known to be accurate once a year or so if you doubt its accuracy.
  9. Triple Jim

    A11 rebuild

    I have a feeling that I'm missing something. If it's a 20 uF capacitor, measuring 20.69 seems to be well within spec, at less than 4% high.
  10. Triple Jim

    MEP 003A Alternator Voltage Regulator Wiring

    Ray has it right... of the three on the bottom of the regulator, the two non-red wires are AC in from the alternator and are interchangeable, and red is DC out to the battery. The other two wires just go to and from the fuse.
  11. Triple Jim

    MEP002A low voltage on one leg.

    110v and 108v are not very different... less than 2%. I would not consider that to be a problem. Frequency (Hz) will not change with a voltage adjustment. To change frequency you need to adjust the engine speed. If you can't raise the engine speed with the big black knob, then something is...
  12. Triple Jim

    Hybrid MEP?

    That should work fine for measuring coolant temperature, but just twisting the thermocouple wires together does not make a very reliable junction. Are you sure they're not twisted and then welded or soldered? I've done things like this quite a few times when I wanted to be able to connect a...
  13. Triple Jim

    Hybrid MEP?

    Yes, and it appears to be black, so probably type J.
  14. Triple Jim

    Soft start on 3/4 hp water pump

    That looks like a nice soft start unit, thanks. Micro-Air says that running current is not reduced, so I think you're just seeing the normal running currents that vary as the indoor and outdoor temperatures change. That 13.5 amps is the maximum expected current with the worst temperatures you...
  15. Triple Jim

    Power Converter Question

    What is the 500 watt load?
  16. Triple Jim

    About to join the generator club.

    Most electronic devices have a power supply as their first entry point of AC power. Those power supplies then provide DC to the actual circuitry of the device. They usually have a wide range of acceptable voltages and frequencies, and are not particularly sensitive to non-perfect AC waveforms...
  17. Triple Jim

    killing my MEP003

    One problem is that without a battery, the high amount of ripple on the battery charging circuit often destroys the RF noise suppression capacitors at the fuel pumps and maybe other locations I can't think of. If one of those decides to become a short circuit, you'd lose all 24v.
  18. Triple Jim

    MEP-003A Bridge Rectifier Assembly Board R1 Resistor value

    If it were mine, I'd attach a meter to the two ends of the resistor with alligator clips so I could read the voltage across it without having to get to it with probes. (You probably already did this.) To cause that resistor to overheat so much that it make a popping sound in a few seconds...