I'd assume the ADVR-054 requires a minimum AC voltage across it's to sense leads for it to generate any field voltage.
Did you measure what residual AC voltage the new regulator has across it's sense leads?
Could be the residual AC voltage the generator puts out is too low for the new regulator...
Just as a reminder for others reading this thread in the future.
NEVER temporarily bypass the QUAD Mod fuse with a jumper unless you are absolutely certain the the Voltage regulator is good.
Why? The primary purpose of the fuse is to protect the Quad winding from a shorted out voltage...
Direct sunlight make a huge difference in solar panel output.
With indirect sunlight my solar panels put out 150-300 watts.
With direct sunlight they kick out 1,700 watts.
Looks like both CR1 and CR2 have been replaced based on the solder blobs and corrosion on their leads in the pics.
V5 looks baked too. Ought to be red in color.
Drop in replacemets for them are available. Crazy expensive though.
If you don't care if replacements are drop ins you can get less expensive wire wound resistors and modify the plate as needed to mount and wire them.
A replacement for #48 is a FSOT2011E7R500JE. They are available from Mouser...
From top to bottom...
R10 thru R13 are the burden resistors for the over current circuit and the %Load Meter circuit.
R14 is part of the field flash circuit
CR2 is part of the field flash circuit
R15 is a current limiting resistor for the Battleshort and AC Interruptor indicator lights
CR1 feeds...
In 3 phase mode...
If you get ~120 VAC at the convenience outlet with S1 in the START position it will indicate a few things. What's likely good and what might be the issue(s) to look into.
If you don't get ~120 VAC at the convenience outlet with S1 in the START position will indicate a few...
You are correct. In 120/240 single phase the AC output should be on L1 & L3 and not L1 & L2. The fact that you are getting no AC on L3 but get it on L2 points to a wiring issue. The Frequency meter is driven by L3. Since there is no AC there that explains why it stops working in 120/240...
PCB and firmware updated to support 2 wire remote start command from battery charge controller or other device commanding the genset to start (like other AutoStart option available).
Basic relay or switch closure to tell genset to start and produce power. Open relay or switch contact to tell...
Some UPS's have a sensitivity setting on them. If yours have it you may want to set them to be less sensitive.
Since UPS's are designed to instantly kick in they will beep when a load kicks on like your heat pump and the line voltage to the UPS dips for a fraction of a second.
They are going...
You might consider renting or borrowing a 3/4 ton or better truck and a car trailer. The car trailer needs to have brakes.
Load the genny onto the car trailer. Chain it down good.
Sure, ad-blocking software does a great job at blocking ads, but it also blocks useful features of our website like our supporting vendors. Their ads help keep Steel Soldiers going. Please consider disabling your ad blockers for the site. Thanks!