Search results

  1. K

    MEP831A DC charging unit problem

    According to the TRC website it's rated at 8 +/- 2 Amps That's the max current with the chargers output shorted. http://tecrescorp.com/3tq/98-19715
  2. K

    MEP-803a overload circuit

    Is the Red Emergency Stop switch accidentally pushed in?
  3. K

    Mep802 small fire repair help !!!

    This from DigiKey appears to be a match. $16 Same dimensions and terminal spacing. https://www.digikey.com/product-detail/en/eaton/TB300-12BS/283-4031-ND/1878310
  4. K

    My “new to me” MEP-804A gen set Question

    You can download the Technical Manuals from here: https://www.steelsoldiers.com/showthread.php?148936-All-the-TM-s-you-need-to-work-on-the-MEP-804A&highlight=804A The first one on the left in the second row (-24P) is the one to look up the part number for the radiator hose. The third one...
  5. K

    Got my 2 MEP-831a's today - got one started - smoked a lot, now won't start

    If the battery is discharged it will cause issues when running since the battery charger will be struggling to bring the battery voltage up. If there is inadequate voltage the Governor Controller, fuel pump and Fault logic will operate erratically until they get adequate DC voltage. Re-try...
  6. K

    803a running @ 130 degrees F after 1 hour+ with no load?

    Could be a bad Temp Sensor Or Temp. Can you check coolant temp by another means?
  7. K

    Looking for MEP-831A Schematics

    The schematic in the TM 13&P dated 15 August 2005 has real clear schematics. Get you hands on a copy of that version. If you can't locate it just PM me your email address and I'll send you a copy of it. Here is a zoom in on the 2005 version.. The newer 13&P dated 30 April 2010 has lousy...
  8. K

    831a oil pressure switch problem solved

    Another member here picked up a 813A kind of recently. Experienced the same Low Oil Pressure issue. Turn out his oil pressure switch went bad. As previously mentioned, be sure to verify oil pressure with a mechanical gauge.
  9. K

    MEP831A recoil start, bleed fuel lines

    Have you adjusted the settings on the SLC10 Governor Control Module per the procedure in the TM? That being the GAIN, BOOST, STABILITY & SPEED adjustments on the Governor Control Module.
  10. K

    802 tripping overload

    The burden resistors, R15 and a few other parts are mounted on a metal plate that's inside the control cube. Open the meter panel and lower it down. Then look on the left side of the back wall of the cube. You should see this with the components you are looking for. (Double click image to...
  11. K

    It finally arrived, MEP-803a

    My 802 came with one installed. It's kept in the garage so I disconnected it. I use a pair of Battery Tenders to maintain the batteries.
  12. K

    Short circuit /overload relay repair help MEP-802A

    The board is soldered to the two terminal strips. The round solder pads on the two edges of the board. That looks to be why the board will not come out. If you have the right solder removal equipment you might be able to unsolder the terminal strips and get the board out. However you risk...
  13. K

    MEP-802 and 803 Main generator tip.

    If you need a MOV I'd be happy to mail you one. PM me if interested.
  14. K

    Need Consoling.....

    You may need to "exercise" the reconnection switch. The contacts may be oxidized from sitting so long and not making good contact. Only exercise the switch with the set shut down.
  15. K

    Generator connection choices

    Vertical metal strap on the lug panel to the right of the Neutral lug
  16. K

    New to me 802

    Also check the rubber cap on the unused water pump port. They tend to dry rot and start leaking coolant.
  17. K

    New to me 802

    My 802 had crap in there too. I had to repair my radiator because when they drained it they damaged it so I had to tear it down to repair it. With patience and a what seems a zillion bolts you can take the sheet metal apart and get in there. Or you can use a shop vac with a skinny tube, as...
  18. K

    Need Consoling.....

    CapePrep, Your load situation is similar to mine here in Mass. I've had an 802 for a few years and it has been more than adequate for my needs. I find I can get by on 1.5 KW to keep the lights on, heat on, fridge running, computers and entertainment center humming along during a storm outage...
  19. K

    MEP 803A will not turn on?

    There is a K8 available on the big auction site....
  20. K

    Safest way to uses a MEP 804b as a backup generator

    You'll only get 208 volts instead of 240 volts across the two phases used. Not sure if any of your 240 loads will care.