Tech data for hose.
CROSS-SECTIONAL SHAPE STYLE
ROUND
INSIDE DIAMETER
4.000 INCHES NOMINAL FIRST END
MINIMUM INSIDE BENDING RADIUS
1.125 INCHES
CONNECTION TYPE
PLAIN BOTH ENDS
FEATURES PROVIDED
OZONE RESISTANT
MAXIMUM OPERATING PRESSURE
5.0 POUNDS PER SQUARE INCH...
What I would have done with the oil, was this. Before changing it, drain a QT out of the set, dump a QT ATF in it, and let it run a half hour. Then change oil. The ATF will clean out lots of sludge and crap. Different stopping times? Could be a lot of things. Could be a main gen bearing. Could...
The CB2 is what controls the DS6. DS6 can only come on when the contacts in the CB2 close. So what we need to do now, is check and see if the wires on S3. The schematics are on the door, and in the books. Can you follow schematics? You need to check each wire # at S3, and what position they are...
As soon as I saw the first pictures, I thought Dewie would jump in! The few times I saw CECOM do any testing, they did a much more professional job of hooking things up.
Reset fault indicator - missed that bright red light somehow - all is well now. THANKS!
No problem. But maybeeeeeeeeeeeeeeeeeeeeeeeeee, looking into the operators TM would be a good way to relax on Sunday? I am not scolding! Nor nagging, much. 😇
Ok, back.
I find that hard to beleve.
1, The set, engine off, S2 in run position. The DS6, (AC output circuit breaker) will not come on.
2. As soon as you start the set, the DS6 comes on.
Now try this. Set off, S2 in the run position. Put S7, (Battle short) in the on position. The DS7...
I don't know what the correct name for the switch that indicates which legs - L1, L2, L3 - are selected. No, I didn't reset the fault indicator.
If you look close by the switch, you will see its marked S6. Its called AM/VM Transfer switch. And all it is used for is to switch what legs get...
Now for another issue with the 804B. Runs great. Connected an ECU to it. During first test, everything seemed to run fine and powered up the ECU once I found the correct setting on the source selector switch. (Source Selector Switch. Tell me what this is?) I shut down the generator each time...
You have not answered my question.
Will the CB2, (Output Circuit breaker) light, (DS2) come on, if the engine is stopped and the S2, (Engine start stop switch) is in the run position?