  1. R

    MEP-803a panel lights flickering

    Out of curiosity have you tried unplugging the main fuel pump, to see if the pump itself is causing a voltage issue? I think you may want to try to find the source of the problem by progressively removing items from the circuit until the issue stops.
  2. R

    MEP-803A: It Runs, It Generates, but it won’t shut off

    I think you may have a slightly different issue with the governor / rack assembly. Your prognosis is good, but if I recall, the springs on the rack only provide OPENING force. To close down the fuel pumps the connection is a lever without springs. Look in the attached picture and my recollection...
  3. R

    MEP-803A: It Runs, It Generates, but it won’t shut off

    Have you load tested the machine yet? It definitely sounds like either the internal rack is not moving correctly ( unlikely due to the way the linkage works ) Or the pump pins are either not in the rack's slots correctly, or not adjusted correctly. Are the fuel inlet lines on all your pumps...
  4. R

    MEP-003A

    Not to side track you away from the solenoid voltage issue, but if you wire the solenoid up ( or even remove it ) and it still won't even smoke out the pipe there are other things going on. Couple questions are: Do you hear the loud click of the glow plug solenoid when you turn S1 to the left...
  5. R

    MEP-003 Water in Exhaust

    Correct, group 24 fits pretty good. The originals were 6TL which were essentially a cube rather than a rectangle. You can still get them from several places but it will be a special order and they can be pricey. Although my commercial price at O-Riley's was about $200 last time I checked, so not...
  6. R

    803a not warming up

    Ah, ok sorry about that. I missed the damaged G17 and thought you were replacing it because you thought it was clogged/dirty. Now I see the light!
  7. R

    MEP-003A

    Ok, so when you test the 2 connections on the solenoid itself you are getting continuity, meaning the coil in the solenoid is good, which you also confirmed by testing the solenoid with 24V. Testing the wires I would expect you should get a tone ( continuity ) when testing from battery negative...
  8. R

    MEP-003 Water in Exhaust

    Bet you can almost smell VICTORY.... and it smells like Diesel!
  9. R

    MEP-003A

    Hey John, I assume you are finding that your solenoid doesn't pull in when you crank it? It will not pull up until you begin cranking, then it will hold there as long as the machine fires up, otherwise it will close down after several seconds. Also, if you have a break in the circuit for the...
  10. R

    Picked up 6 MEP-802A gensets and will be documenting making them all runners here

    I've got to show my son that grapple! He took an old 425 last year and outfitted it with an LPW2 engine. Converted it to 24V and has more lights and flashers on it than most emergency vehicles! He made forks, a weight block and a 2 stage trailer hitch for the 3 point, then he made a hydraulic...
  11. R

    803a not warming up

    I'm telling you... just backflush your old G-17. There's nothing in it besides a screen.... it just keeps large solids out of the pump.
  12. R

    Where to find reasonable genny ?

    Just be careful... says he used it for his well, doesn't say how long ago! The fuel pump is removed and looks like maybe the filter housing as well. Definitely a good buy at $2000, just don't expect to throw batteries in it and off you go.... I'm sure there's more secrets hiding in there than...
  13. R

    MEP-003 Water in Exhaust

    Looking great! Can't wait to hear you say "IT'S RUNNING!" Good luck!
  14. R

    803a not warming up

    I bought the G-17 not too long ago, so you may still be able to find it. ( think I got it from Rock Auto ) but be advised it is a strainer, not a filter so you should be able to remove it and just backflush with carb or brake cleaner.
  15. R

    Where to find reasonable genny ?

    Hello, I have some really nice 002's available. I also have spin on fuel and oil filter conversions that I machine myself available as well. Right now I have 3 002's for sale. All super low hour, Lowest is 7 hours, highest is 250 hours. All fully tested and serviced. Unfortunately none have the...
  16. R

    Picked up 6 MEP-802A gensets and will be documenting making them all runners here

    Here's my take on things.... In the first video I believe it is running on 1 cylinder. It is taking far too long for it to come up to speed and the smoke puffs look like a single cylinder firing not 2, and speed sounds fairly close to 1800. In the 2nd video it sounds smoother, but I still think...
  17. R

    Main breaker CB1 on 002a/003a wiring & diagram.

    Kurt, what is it that you need? A currently functional 002 or 003? if so I can probably provide you with something. I have a few of them here.
  18. R

    MEP-003 Water in Exhaust

    Keep turning the motor. "B" is for setting the valves. You want "PC" on the flywheel. Get it on the PC mark and then verify the position of the #1 intake cam lobe in the picture I posted. Most pumps will spin pretty easily with just 2 fingers to turn it. If it requires your whole hand to...
  19. R

    MEP-003A voltage and phase switch stuck

    The frequency transducers on those machines are unreliable at best! Either replace the gage with a direct read analog or digital gage ( remove the transducer and chuck it ) Or if you like the original gage look, you can pick up a newer style transducer that LITD found for $12 on ebay that will...
  20. R

    Main breaker CB1 on 002a/003a wiring & diagram.

    You can find a lot of info on the main breaker here: https://www.steelsoldiers.com/threads/mep-002a-and-003a-main-breaker.61257/page-4 But post #70 specifically talks about the additional 6 control wires you are talking about.