    Mep806a where is the mpu?

    If you can locate connector P6 the wire for the MPU run from there to the MPU. The wire is a 2 conductor shielded wire so it will appear as a single "wire" from P6. Unfortunately there are 5 wire sets like that running from P6 to various places.
  2. K

    Mep806a where is the mpu?

    It should be screwed into the bell housing where the flywheel would be inside. I can only go by the TM. Never wrenched on an 806. Maybe someone can chime in with a pic or location description
  3. K

    Mep806a where is the mpu?

    No ohms as in almost 0? If so the MPU may be mechanically damaged. Need to remove and inspect the tip of it. They gen damaged if they come in contact with the flywheel.
  4. K

    Generator mep-804b voltage problems

    The VR testing sections "should" be the same. Major different between the A & B is which engine it has.
  5. K

    Mep806a where is the mpu?

    TM 9-6115-645-24 See Section 2-110 Magnetic Pickup Has testing and adjustment procedure.
  6. K

    Mep806a where is the mpu?

  7. K

    Generator mep-804b voltage problems

    It's not in that manual. You'll need to download TM 9-6115-643-24. It's available in the TM section of the forum. In here Generator TM's
  8. K

    803 won't restart without resetting Dead crank/normal switch

    Going to need to track down the cause. I'd suggest doing the following. 1) Start the set 2) Shut the set down and leave the Dead Crank switch in NORMAL 3) Move S1 to the PRIME/RUN position Does the fuel pump run then or not? Do the panel lights work? If no fuel pump or panel lights then then...
  9. K

    803 won't restart without resetting Dead crank/normal switch

    There is no need to put the Dead Crank switch in the OFF position after shutting the set down using the Master switch S1. Something is wrong with the set if it won't start without cycling the Dead Crank to OFF and back to NORMAL. Having the Dead Crank switch in the OFF position removes most of...
  10. K

    Generator mep-804b voltage problems

    Have you downloaded the TM and performed the VR tests? If so what were the results?
  11. K

    MEP 804B

    Yes it's referred to as Motion Transducer in the TM
  12. K

    Mep806b challenges

    So a 2 1/2" is needed? If so 2 1/2" Spacer
  13. K

    Mep806b challenges

    A less expensive option is to use these. About half the cost. Just need to use 10-32 screw instead of a nut. 1 1/4 spacer
  14. K

    Mep806b challenges

    NSN seems to indicate the length of the hex is 1.25", not the 1.5" you measured. Assuming it's 1.25" I found these. Standoffs Be sure to check specs vs the busted ones you have to verify they'll work.
  15. K

    Mep806b challenges

    What length is the hex, the threaded portion and what size and pitch are the threads? How many types? Hex with internal threads on both ends, hex with threaded stud, other?
  16. K

    Gen set 804A 15k No volt, no freq

    Actually the MWO for the 804A calls for a KTK-3 fuse. FNQ-R-3 is only for the 802A & 803A
  17. K

    Leak: Thoughts before degreasing and diagnose

    Can you measure the hole diameter for the missing LED lens with some calipers? I can look around at parts suppliers and try to locate suitable replacements.
  18. K

    MEP-003A , MEP-004A, MEP-005A, MEP-006A Replacement A4 & A5 Card Interest

    Assemblies now available the the Classifieds. Click on link in my signature
  19. K

    MEP 804B

    IAW = In Accordance With
  20. K

    Mep806b challenges

    Be sure your meter is set to AC volts when adjusting the MPU.