I need to ask the obvious question - why are you wanting to do this?
As an aside, the 004 and 005 generation machines can be wired single phase. It is a bit of work but possible.
One thing you may want to do is check out the prices govplanet is getting for generators at the closest depot to you. Take the auction price and add 30%. That is about what a bidder will pay for a unit after fees and taxes.
With that info you better judge the market conditions in your area.
These are prime rated sets. That means they can be run at their full rated load indefinitely. The rated load is 10kw. The set can produce more power than that. That extra should be considered reserve power for transient events such as starting an inductive load. The 52 amps includes the reserve...
Well, no. 52 amps resistive at 240v is 12.5 kw. The meter is calibrated for a 0.8 power factor. If you look at the gauge most of them have a red line at 80% which for a pure resistive load is your 100%.
Edit
If you have the voltage dialed down to 220v it’s 11.5kw.
Either way it’s over 100%.
Check and see how much fuel you have returning to the tank with it not running in prime and with it running under some load. It’s ok for the return flow to drop a little but you should still get a nice stream back to the tank.
The answer isn't really standardized since how much load and how long at each load should be based on what you are trying to do. If its routine run I'll do 15min each at 25%, 50%, 100%, 50%, 0%. If I'm in a hurry, I'll warm it up a bit then 50% for 15 min and 100% for 15 min.
If I'm clearing...
How to phrase this.. You see, when a daddy generator... Nevermind.
I've long given up on the creativity of the people handling these sets before the auctions buyers get them.
You are going to want to pop all the covers off and give it a really good once over. Take it apart and post up more...
I expect you could put a strong magnet on the pan adjacent to the drain location to capture any magnetic fines in the oil.
Remove the magnet as the oil drains and the fines should flow out with the oil.
With the size and strenght of rare earth magenets available, you should have an even...
I've installed Fumoto oil drain valves on virtually everything I own. Makes changing the oil a LOT easier on the equipment with larger sumps.
I'll be changing the oil on the M1081 this summer and I plan to add one to it as well.
+1 on not worrying too much about exhaust noise.
You will get far better results from building some sound isolating walls to put up around the engine itself. I have a MEP003 with the ASK and it made a very noticeable difference to reduce the clacky higher frequency sounds that can be harsh...
The most problematic part of the generator is the speed control module. I strongly recommend having a spare on hand. You can get by if it fails by pinning the speed control to MAX with the sacrifice of fuel econ and noise. Buy the one that Kurt here on the forum builds. Also buy one of his power...