  1. Scoobyshep

    Generator Hook up 1 phase zig zag or double delta

    I have been using a zigzag for years on a 004 and it actually does use all 6 windings. Sent from my SM-G973U using Tapatalk
  2. Scoobyshep

    Hookin up 806a: Remove 52-12 plug?

    I used to buy it by the foot from garvin industries. Sent from my SM-G973U using Tapatalk
  3. Scoobyshep

    Hookin up 806a: Remove 52-12 plug?

    You need bushings on the conduit, and make sure to use a piece of flex.
  4. Scoobyshep

    806 no crank on low fuel?

    float= discreet signal (1 or 0, voltage or no voltage) sending unit= analog signal (variable resistance t0 swing the gauge
  5. Scoobyshep

    Hookin up 806a: Remove 52-12 plug?

    That is a pin and sleeve. It looks like it might have been added. (My hands on with the 80x series is limited) I have seen these hard wired, pin and sleeve, camlock, etc. as long as the connecting means is rated for the voltage and current its fine
  6. Scoobyshep

    Tank Blanketing, for long term storage on big tanks?

    I seem to recall argon not being as expensive, maybe my supplier has a discount or something.
  7. Scoobyshep

    Tank Blanketing, for long term storage on big tanks?

    Atmosphere is 70 some odd % n2 already. If i were to do a gas blanket it would be argon. I store fuel in 6 gallon tanks and i have had really good luck with biocide. Sent from my SM-G973U using Tapatalk
  8. Scoobyshep

    240V 3ph on MEP-806B. Is it safe?

    100% yes you need to ground the frame of the treater to the generator frame. Technically you really should have a breaker between the generator and treater, mainly because the generator breaker is made to protect the generator, it can put out more current than desired for the treater and wire.
  9. Scoobyshep

    240V 3ph on MEP-806B. Is it safe?

    Bonding: Make sure the neutral (L0) is electrically tied to the chassis, The machine needs to be grounded back to the generator frame as well. It is also a good idea to have a ground rod (this way the ground reference is the same as the ground). If it is impractical to have a ground rod (it...
  10. Scoobyshep

    240V 3ph on MEP-806B. Is it safe?

    I had an apprentice reverse phasing on a conveyor accidently one night, he ended up teepeeing 2 boats. Sent from my SM-G973U using Tapatalk
  11. Scoobyshep

    240V 3ph on MEP-806B. Is it safe?

    Remember proper bonding. If its only powered from the generator it is a separately derived system, so the neutral needs to be bonded to ground. Sent from my SM-G973U using Tapatalk
  12. Scoobyshep

    240V 3ph on MEP-806B. Is it safe?

    Does your hook up have a neutral? If it does then something uses 120. Of they are rated at 220 then 208 will be just fine. Sent from my SM-G973U using Tapatalk
  13. Scoobyshep

    MEP806 wheel kit DIY or ?

    Are you going to be moving this once and that's the end of it or do you want it movable for its lifetime? Sent from my SM-G973U using Tapatalk
  14. Scoobyshep

    240V 3ph on MEP-806B. Is it safe?

    Okay this changes things slightly, you need to look at your equipment and see if there is anything that runs 120 volt. If there isn't anything requiring 120 then you can Crank It Up. Also look at the motors and see if they have anything on the nameplate saying usable at 208. Sent from my...
  15. Scoobyshep

    240V 3ph on MEP-806B. Is it safe?

    You can get 240. BUT the leg to ground voltage will increase as well. Leg to ground is typically 120. Sent from my SM-G973U using Tapatalk
  16. Scoobyshep

    MEP806A Double Delta Single Phase

    Do yourself a favor and get a load (a floodlight or heater goes a long way) on the unused leg. Pad wise I would pour one, but thats just my opinion Sent from my SM-G973U using Tapatalk
  17. Scoobyshep

    MEP806A Double Delta Single Phase

    Thats where things get tricky. Double delta and zigzag are not commonly used. The last time I had set one of these up they were 3 single phase transformers that we wired together As for kva its all about the amperage you want, It wont produce more than you put in (generator is 60 kw you wont...
  18. Scoobyshep

    MEP806A Double Delta Single Phase

    unless the compressors are a dual speed no, they draw the same current weather cooling or heating. There are many ways to set this up so there isnt a singular answer. Fast and easy use 2 legs, which gives you 208 volt transformer delta to delta 240 volt but 2/3 capacity...
  19. Scoobyshep

    Help-50amp rv plug to mep 002a

    Black to L1 red to L3 white to L0 bare to chassis (there is a lug on the front of the set below the control panel on the frame)
  20. Scoobyshep

    Help-50amp rv plug to mep 002a

    That switch selects what the volt meter is connected to. In single phase mode you only need the 2 most clockwise positions. most clockwise is L3 to L0 and should read approx 120 the other is L1 to L3 and should read approx 240. I am only seeing 3 conductors, there should be 4.