  1. jbk

    10 kw tactical quiet generator

    theirs a ground lug inside your set at the bottom of the output lugs. run a wire from it out the wire boot on the side to the trailer ground.
  2. jbk

    10 kw generator mep 803a

    thier was a bullitin on the 5 and 10 kw tqg sent to all services a few years back. i have it stored somewhere just couldnt find it tonight. the problem was with the a1 bridge rectifier circut. if the gen. is held in the start position to long voltages can peak at over 400 vac across the quad...
  3. jbk

    10 kw generator mep 803a

    this is on my 802 its the same.
  4. jbk

    MEP-002A Gauges inoperative

    one of mine did this. the only meter that worked was the dc charging. it turned out to be the ground strap underneth the control panel box. the aluminum oxidized badly, cleaned it up.
  5. jbk

    10 kw generator mep 803a

    not only the exhaust but the set also has the radiator hot air exit though the top .
  6. jbk

    mep002a vibration

    the 002 is going to vibrate alot more than the 003, nature of the beast. i was going to suggest adjust valves as this made a big differance to mine. might recheck, if out a little it can make a big differance(vibrate). it will run on one cylinder but will take its time to come to speed. try...
  7. jbk

    Looking for genset-related wisdom

    i dont know anything about this set, but have seen them come up for auction, nice motors. 7.5 kw 28 volt dc. their should be some output lugs somwhere. i guess you could see if its making correct voltage. maybe someone off grid might have a use. lots of dc amps.
  8. jbk

    Ideas for "Making Portable" MEP-017A?

    heres my 018a on a homemade trailer, my 016a on casters from hf. and my 017a on furniture dollys from hf. ive also used the little hf. trailer.
  9. jbk

    mep-106b lugs

    this is a fuel pick up i have for diesel. compresion fittings non collapseable 20 ft. fuel line, all millitary surplus. i have 55 gal. or this 15 gal. drum. the other pictures are of a 017 gas gen. with barb. fittings.
  10. jbk

    mep-106b lugs

    yes strip the wire (i solder the end) run it throgh the split bolt. i have a similar 016a set 3 kw. when set to 120 volt single phase it will make 30.2 amps. so 10 ga. wire should do it.
  11. jbk

    10 kw generator mep 803a

    sure sounds like a rod knocking to me.
  12. jbk

    Make a low trailer for MEP-002A

    i mounted one of my 002s on a h.f i put a longer tounge on it the one with it is short and flimzy. picture of my 003 on a civi trailer.
  13. jbk

    1950's Onan powered light set

    try posting this over at (smokstak) post it under onan generators somone might know something. try to get model spec. and srerial no. i dont think its military, note the plug wires unshielded.
  14. jbk

    1950's Onan powered light set

    looks like an civilian onan cck engine usually in the 5kw range. almost looks like a piece of highway equipment and may not be 50s vintage i dont think the cck eng. goes that far back it also has a alternator not gen. on it.
  15. jbk

    mep-004a starting issue

    the top of the injection pump. remove the return line unscrew the tee. its that brass that screws into the top.
  16. jbk

    mep-004a starting issue

    mine did this, it was that check valve on top of the solinod cover on injection pump. just remove the glass ball in the brass and your good to go.
  17. jbk

    10 kw tactical quiet generator

    old thread, i guess your talking about this mod. to the v/r just remove wire under #8 ter. on v/r splice in the fuse holder. this is on my 802a, hopes this helps.
  18. jbk

    MEP003 Voltage selector switch

    ive had a few that did it. yes remove the a/c box side cover and loosen the bolts on the switch even one. i taped the knob and it would turn once i get it on 120/240 i dont mess with it again. dont force it. these switches get alot of dirt in them. if you wont to attempt flushing with contact...
  19. jbk

    Generator Identity

    the 017a is 5kw, 2 cyl. 42 ci. engine . ive load tested mine at 7.5 kw. they use about a gallon per hour. very loud 82 db. at 25 ft. the cover is an someones add on. good unit for the $
  20. jbk

    Looking at MEP-002a... advice

    try to bring a load bank with you. 4(6kw) small 1500 watt heaters work good. this will put some preasure on the rods(listen for adnormal knocks) and will check govenor adjustment.