I had a blue S1 switch that would hang on the start position. I replaced it with an Electroswitch 75902LV: this is Rev 3 of the S1 and is a better quality switch.
Your AM-VM switch indicates amps between specific terminals. I use a 240 volt stove for my load bank and it provide a balanced...
Drop the control panel down to get access to S1 and S6: I sprayed contact cleaner in the various holes in the body of the switches. The Blue switches have a lot of openings in the body and I sprayed a wee bit of contact cleaner in each and simply turned the switch 25 or so times. You are...
It's good to exercise S1, S6, S8. S1 and S6 are easy to get to with contact cleaner. S8 not so much. You are just trying to remove any corrosion that has accumulated during storage so you get good electrical contact through the switch. You have pictured S8 and S6.
I've been lucky with my 2 load meters and have been able to calibrate them using a clamp on meter. I do have one volt meter that does not calibrate accurately. As Diesel points out they are not very accurate to begin with. Sounds like you will need to replace what you've got....search SS for...
Operating a stand-alone MEP generator without a driven ground rod is not safe.
You can get voltage and amps from the main lugs with an ungrounded MEP-803A......Which is why you should ground the generator.
https://www.steelsoldiers.com/attachment.php?attachmentid=716277&d=1516645419
0005-2...
Yep. F03A125V30A is the same as BUS ABC-30-R. Mouser has a WAY better price than the one I posted above : https://www.mouser.com/productdetail/bussmann-eaton/bk-abc-30-r?qs=St27ATL478s0HesTffljHg%3D%3D
Mouser has them for around $22 for 10 fuses. You ALWAYS need spares...... https://www.mouser.com/productdetail/bussmann-eaton/bk-abc-30-r?qs=St27ATL478s0HesTffljHg%3D%3D
I hear you. I used to live in the country on 100 acres.....parked anything I wanted anywhere. I retired and move to the city and now I have to stack my stuff in the drive....no more free wheeling. City rules and such. Next door neighbor accused me of turning the neighborhood into an FOB with...
I've never seen a magnex-ug-transformer - I wired my generator through the house's breaker box. And I don't think I'd leave my generator 600 ft from my house.
TMs for your machine here: https://www.steelsoldiers.com/showthread.php?155892-All-the-TM-s-You-need-for-the-MEP-006A
Usually some good troubleshooting tips in the TMs.
You need a single ground to neutral bond in the system, so yes. However, I've made a work around so I don't have to repeatedly connect / disconnect my machine's ground to neutral bonding strap. I use an electric stove as a load bank and my ground to neutral bond is in the stove. When I...
Talk with the friendly folks at Electroswitch for a 75902LV: https://www.steelsoldiers.com/showthread.php?170926-MEP-802A-803A-S1-Master-Switch-Source-Electroswitch
3,500 watts/.8 (military de-rating)=4,375 max watts/240 volts=18.2Amps. Looks like 20 amps to me, too. My house and generator are 240/120 volts.
I am assuming this generator is de-rated like my MEP803A.
You indicate a 220 volt reading. If so 4,375/220 = 19.9 amps. I forget how accurate the...
"2nd Run 1st Load Configuration: Installed a four outlet receptacle box to the terminal lugs. Configuration is two outlets hot leg on L1, the other two outlets hot let on L3, both neutrals on L0, both grounds on G, L0 to G bar installed, no grounding rod present."
Install a ground rod...