Search results

  1. K

    Just got a 1994 MEP-802a Has a few issues..

    The coolant leak may by from the rubber cap on the unused nipple on the water pump. My 1997 802 leaked there when I first got it. Found the rubber cap had dried out and cracked. Easy fix. See TM 9-2815-252-24P Figure 3 (Cooling System) item 11
  2. K

    MEP 805B CMOS Voltage

    According to TM 9-6115-671-14 page 2-13 the CMOS voltage light indicates.... CMOS voltage. If indicator is lit, indicates voltage necessary for CMOS device operation is too low. If not lit, CMOS device voltage source is sufficient. Lots of good information in the table regarding the diagnostic...
  3. K

    Heating a S280

    How about getting a used propane "furnace" from a trailer or camper? They pull air in from the outside, use it for combustion and then vent the combustion outside again. I put one on my car trailer/camper. Works great. It does require 12 v power to run the igniter and the blower. Only required...
  4. K

    MEP-802A Alternator Wiring Diagram

    Best I could get for you with my phone... http://i28.photobucket.com/albums/c205/kloppk/MEP-802a/20150914_125733_zpsveliufar.jpg http://i28.photobucket.com/albums/c205/kloppk/MEP-802a/20150914_125619_zpswiciyown.jpg
  5. K

    remote start mep-802a's sold on G/L a week or so ago....

    Pins U, P & R on the diagnostic port could be wired up to provide for Remote Start. U to P & R for Start U to R for Run At the moment I don't see a means to close the contactor thru the diag port...
  6. K

    MEP-802A Master Control Switch. It's an 88-21160 NSN:5930-01-368-5160

    Electrically it looks like it should work according to the switch contact tables in the two TM's. Just need to use the correct terminals on the switch from the -002.
  7. K

    MEP-802A Master Control Switch. It's an 88-21160 NSN:5930-01-368-5160

    Last one I bought was from ebay. PN 75902LV I don't see any listed there now though. See http://www.steelsoldiers.com/archive/index.php/t-80554.html
  8. K

    Charging 24v series with 12v question ?

    Some battery chargers have their Negative output connect to the AC line cord ground pin. IF the battery chargers have a 3 prong plug AND it's outputs are isolated from the line cord ground pin then there is not need to disconnect the cable(s) from the batteries. If the chargers Negative...
  9. K

    MEP803A Filters

    Fuel Filter Cartridge WIX 33348 Fuel / Water Separator WIX 33472 Oil Filter WIX 51374 Belt Goodyear 4040355
  10. K

    Finally Joined The MEP Family

    Grab a copy of TB 9-6115-642-13 It has all the info on the operation of the heater. Essentially it burns diesel fuel and circulates warmed coolant thru the engine block.
  11. K

    24v Battery chargers

    I use a pair of the 12 V Deltran Battery Tender Jr's on my 802A. $26 on Amazon. Just wired each charger/maintainer to each of the batteries. Not need to disconnect the batteries from each other or from the genny. The charger outputs are "floating" so no issues with connecting the positive of...
  12. K

    MEP-803A starting Help

    24 V, My bad. Thinking conventional system. Post updated.
  13. K

    MEP-803A starting Help

    Does the fuel pump run with S1 in the Run position? Is the S17 Emergency Stop switch pulled out? Is the Battle Short Switch in the down position? The 24 volt power path from the battery to S2 is... battery-starting solenoid-charging meter shunt-diode CR1-dead crank switch-Emergency Stop...
  14. K

    MEP 803a Fuel Drain?

    The thread size and pitch for the A3816 well nut is 3/8-16 thread size
  15. K

    10 KW Gen Heads

    According to the PN it looks like they are for the MEP-003A
  16. K

    Mep-802a overload capacity

    Resistive loads are a 1.0 power factor. With a 1.0 PF load the 802 can provide 5000/0.8=6,250 Watts If you are running a purely resistive load such as a water heater and incandescent lights it should happily put out 6,250 watts and would be at 100 % load on the meter. I verified this yesterday...
  17. K

    Mep-802a glow plug source?

    The part number is 186-6264. Onan and Cummins....
  18. K

    dc alternator mep803a -- need part number for the pulley

    My parts manual TM 9-6115-642-24P indicates its a 88-20003 Here's a replacement: http://www.southernautomotive.com/catalog/product_info.php/products_id/1006
  19. K

    MEP 803a Fuel Drain?

    The A3816 appears to be a basic Well Nut. http://www.bylerrivet.com/products/item-details.aspx?pid=633 You might be able to unscrew the old valve from old well nut. If it no too deformed you may be able to insert it back into the tank and then screw the valve back it expanding the well nut...
  20. K

    MEP-803a Fuel and oil filters

    Fuel Filter Cartridge WIX 33348 Fuel Filter Cannister WIX 33472 Oil Filter WIX 51374 Belt Goodyear 4040355