  1. DieselAddict

    The MEP-831 goes to the track

    Maybe put a generator engine in something. :D
  2. DieselAddict

    The MEP-831 goes to the track

    Absolutely. The team did a great job driving. Only a couple black flags and no broken parts. Placed 17th out of 98.
  3. DieselAddict

    Two MEP-831a generators in parallel?

    I've been wanting to see if the timing circuits could be modified to accept an external reference. I have a couple of parts units and its on my list of things to do once I have a few other things scratched off the list. I need to find a stator for an 831 to make that happen. If anyone has one...
  4. DieselAddict

    The MEP-831 goes to the track

    Had several people try to pry the generator and refer units out of my hands with money. Nope. :D
  5. DieselAddict

    The MEP-831 goes to the track

    I've not been on the forum so much lately or online in general due to a lot of changes on this end. Non life threatening thankfully. Last weekend I took the time to go to the track for the weekend. We borrowed a friends camper and I decided to use the MEP-831 for power since its usually a...
  6. DieselAddict

    MEP-802a Power Quality (With oscilloscope pics)

    Put the 802 in 3 phase mode and see what it looks like.
  7. DieselAddict

    mep-802a no start well pump

    I apologize but I'm having trouble following you. You connected the generator and turned on your stove. What was the load meter reading when it tripped on overload? How long did it take? Was the engine exhaust smoking? We need a LOT more info to help you.
  8. DieselAddict

    mep-802a no start well pump

    Need to know more about the situation. When you say stops it cold does that mean the engine bogs down? What happens to the load meter and the volt meter? Can you shoot a quick video of the event? Have you load tested the generator? I have a 3/4 horse well pump at 180' and a MEP831 starts...
  9. DieselAddict

    MEP 831 FAQ for owners or potential buyers

    You'll want to grab the Technical Manual from the manual section of the forum and do a bit of quick reading to get up to speed on how these things work. If you have power at the receptacle but not the lugs (assuming you flipped the switch) you need to troubleshoot the circuit that energizes...
  10. DieselAddict

    MEP-831a Troubleshooting

    Right, if you loose oil pressure it is supposed to shut down. I should have some time on Sunday to help.
  11. DieselAddict

    MEP-831a Troubleshooting

    If the oil pressure light is on you will not get any control power. Nothing will work. The hour meter will not work. While its running with the oil light on click the start/run switch off and back on quickly enough that the engine doesn't shut down.
  12. DieselAddict

    MEP-831a Troubleshooting

    Standard wiring convention is to use RED and BLACK for load, WHITE for neutral, and GREEN as ground. This might be a little late in the process to ask but what is your experience with wiring of this type? Are you comfortable with doing residential power wiring?
  13. DieselAddict

    MEP-831a Troubleshooting

    No. you can not do that. The internal wiring can not support more than 10 amps. You will set it on fire.
  14. DieselAddict

    MEP-831a Troubleshooting

    You can't change the breaker to the factory outlet. The wiring inside won't handle that much power. You will want to install an outlet on the main lugs of the generator. I'll be happy to help with the generator. Looks like you are only about an hour away if you want to drag it over to Efland.
  15. DieselAddict

    MEP-831a Troubleshooting

    Its pretty simple. You use a spring scale and adjust the magnet to get a pull-off force of 4 lbs +\- 0.25 lbs. disconnect the governor rod from the governor bracket and use that hole to connect the scale.
  16. DieselAddict

    MEP-805a reconfigure to single phase

    Couple of items to unpack here. 1. This unit does have a true neutral. This is a 3 phase Y and not a 3 phase delta. If the AC unit requires a neutral that is no problem. 2. Do NOT set your VR higher to try and get closer to 240v between main phases. It is not necessary for modern appliances...
  17. DieselAddict

    LOOK! Jackpot! :)

    My main goal is to improve the scans we have available now. Especially for the diagrams that have been really hard to read in the PDFs. Also I've not seen the coursework documents as PDFs before. I'm going to look through those and see if there are tips and tricks that would benefit the...
  18. DieselAddict

    MEP 802A Fix-up Thread

    If you didn't remove them you are OK.
  19. DieselAddict

    LOOK! Jackpot! :)

    I received a huge care package from an anonymous donor. I have a LOT of good stuff to go through. The circuit drawings are readable!! They are much better than the scans we have access to now. I will post more once I've given them a look over.
  20. DieselAddict

    MEP-802/803/831 Generator Control & Parameter Monitor by WIFI Demo

    The system should have more than enough range to make that happen. I can control mine from down the block. :D